4–20 mA to -50–150 °C: scaling table

A transmitter calibrated -50–150 °C: 4 mA = -50 °C, 20 mA = 150 °C. Linear output.

At a glance

Span
200 °C
Change per 1 mA
12.5 °C
Change per 1 %
2 °C
Value at 12 mA
50 °C

Scaling table

Current (mA)Output (%)Value (°C)
4.000 %-50
6.0012.5 %-25
8.0025 %0
10.0037.5 %25
12.0050 %50
14.0062.5 %75
16.0075 %100
18.0087.5 %125
20.00100 %150

Open this range in the 4–20 mA converter

NAMUR NE 43 limits in °C

Current (mA)Value (°C)Meaning
3.6-55Failure signal, downscale (≤ 3.6 mA)
3.8-52.5Lower measuring limit (3.8 mA)
20.5156.25Upper measuring limit (20.5 mA)
21.0162.5Failure signal, upscale (≥ 21 mA)

Formula

PV = -50 + (I − 4) / 16 × 200 °C

Example: a reading of 13.6 mA corresponds to 70 °C. Going the other way, 100 °C corresponds to 16 mA.