4–20 mA to 0–150 °C: scaling table

A transmitter calibrated 0–150 °C: 4 mA = 0 °C, 20 mA = 150 °C. Linear output.

At a glance

Span
150 °C
Change per 1 mA
9.375 °C
Change per 1 %
1.5 °C
Value at 12 mA
75 °C

Scaling table

Current (mA)Output (%)Value (°C)
4.000 %0
6.0012.5 %18.75
8.0025 %37.5
10.0037.5 %56.25
12.0050 %75
14.0062.5 %93.75
16.0075 %112.5
18.0087.5 %131.25
20.00100 %150

Open this range in the 4–20 mA converter

NAMUR NE 43 limits in °C

Current (mA)Value (°C)Meaning
3.6-3.75Failure signal, downscale (≤ 3.6 mA)
3.8-1.875Lower measuring limit (3.8 mA)
20.5154.688Upper measuring limit (20.5 mA)
21.0159.375Failure signal, upscale (≥ 21 mA)

Formula

PV = 0 + (I − 4) / 16 × 150 °C

Example: a reading of 13.6 mA corresponds to 90 °C. Going the other way, 112.5 °C corresponds to 16 mA.