A transmitter calibrated 0–16 bar: 4 mA = 0 bar, 20 mA = 16 bar. Linear output.

At a glance

Span
16 bar
Change per 1 mA
1 bar
Change per 1 %
0.16 bar
Value at 12 mA
8 bar

Scaling table

Current (mA)Output (%)Value (bar)
4.000 %0
6.0012.5 %2
8.0025 %4
10.0037.5 %6
12.0050 %8
14.0062.5 %10
16.0075 %12
18.0087.5 %14
20.00100 %16

Open this range in the 4–20 mA converter

NAMUR NE 43 limits in bar

Current (mA)Value (bar)Meaning
3.6-0.4Failure signal, downscale (≤ 3.6 mA)
3.8-0.2Lower measuring limit (3.8 mA)
20.516.5Upper measuring limit (20.5 mA)
21.017Failure signal, upscale (≥ 21 mA)

Formula

PV = 0 + (I − 4) / 16 × 16 bar

Example: a reading of 13.6 mA corresponds to 9.6 bar. Going the other way, 12 bar corresponds to 16 mA.