4–20 mA to 0–100 %: scaling table

A transmitter calibrated 0–100 %: 4 mA = 0 %, 20 mA = 100 %. Linear output.

At a glance

Span
100 %
Change per 1 mA
6.25 %
Change per 1 %
1 %
Value at 12 mA
50 %

Scaling table

Current (mA)Output (%)Value (%)
4.000 %0
6.0012.5 %12.5
8.0025 %25
10.0037.5 %37.5
12.0050 %50
14.0062.5 %62.5
16.0075 %75
18.0087.5 %87.5
20.00100 %100

Open this range in the 4–20 mA converter

NAMUR NE 43 limits in %

Current (mA)Value (%)Meaning
3.6-2.5Failure signal, downscale (≤ 3.6 mA)
3.8-1.25Lower measuring limit (3.8 mA)
20.5103.125Upper measuring limit (20.5 mA)
21.0106.25Failure signal, upscale (≥ 21 mA)

Formula

PV = 0 + (I − 4) / 16 × 100 %

Example: a reading of 13.6 mA corresponds to 60 %. Going the other way, 75 % corresponds to 16 mA.