4–20 mA to 0–100 %: scaling table
A transmitter calibrated 0–100 %: 4 mA = 0 %, 20 mA = 100 %. Linear output.
At a glance
- Span
- 100 %
- Change per 1 mA
- 6.25 %
- Change per 1 %
- 1 %
- Value at 12 mA
- 50 %
Scaling table
| Current (mA) | Output (%) | Value (%) |
|---|---|---|
| 4.00 | 0 % | 0 |
| 6.00 | 12.5 % | 12.5 |
| 8.00 | 25 % | 25 |
| 10.00 | 37.5 % | 37.5 |
| 12.00 | 50 % | 50 |
| 14.00 | 62.5 % | 62.5 |
| 16.00 | 75 % | 75 |
| 18.00 | 87.5 % | 87.5 |
| 20.00 | 100 % | 100 |
NAMUR NE 43 limits in %
| Current (mA) | Value (%) | Meaning |
|---|---|---|
| 3.6 | -2.5 | Failure signal, downscale (≤ 3.6 mA) |
| 3.8 | -1.25 | Lower measuring limit (3.8 mA) |
| 20.5 | 103.125 | Upper measuring limit (20.5 mA) |
| 21.0 | 106.25 | Failure signal, upscale (≥ 21 mA) |
Formula
PV = 0 + (I − 4) / 16 × 100 %
Example: a reading of 13.6 mA corresponds to 60 %. Going the other way, 75 % corresponds to 16 mA.
Need a 4–20 mA pressure or level transmitter?
Request a quote at SensorSpan