Resistance of a single copper conductor at 20 °C. For a loop, count both conductors.

AWG sizes

SizeDiameter (mm)Cross-section (mm²)Ω/kmΩ/1000 ft
AWG 102.5885.2613.2690.9965
AWG 122.0533.3095.1981.584
AWG 141.6282.0818.2662.519
AWG 161.2911.30913.144.006
AWG 181.0240.82320.96.37
AWG 200.8120.517633.2310.13
AWG 220.6440.325552.8416.1
AWG 240.5110.204784.0125.61
AWG 260.4050.1288133.640.72
AWG 280.3210.08098212.464.74
AWG 300.2550.05093337.7102.9

Metric sizes

SizeDiameter (mm)Cross-section (mm²)Ω/kmΩ/1000 ft
0.14 mm²0.4220.14122.937.45
0.25 mm²0.5640.2568.820.97
0.34 mm²0.6580.3450.5915.42
0.5 mm²0.7980.534.410.49
0.75 mm²0.9770.7522.936.99
1 mm²1.128117.25.243
1.5 mm²1.3821.511.473.495
2.5 mm²1.7842.56.882.097
4 mm²2.25744.31.311
6 mm²2.76462.8670.8738

Calculated with ρ = 0.0172 Ω·mm²/m (copper at 20 °C), the value used by the loop power and RTD wiring calculators. AWG diameters follow d = 0.127 mm × 92^((36 − n)/39) for solid wire. Resistance rises about 0.39 % per °C; stranded and tinned conductors are slightly higher.