What VPD means
The saturation vapour pressure is the most water vapour the air can hold at a given temperature. The vapour-pressure deficit (VPD) is the gap between that maximum and the water vapour actually present:
- VPD = es · (1 − RH/100) kPa
A large VPD means dry air with a strong pull on water; a small VPD means the air is close to saturation. It is the quantity used when the drying power of air matters — greenhouses, drying rooms, paint booths, clean rooms and HVAC — while relative humidity is the quantity used when condensation on a surface is the question.
The FAO-56 formula
FAO Irrigation and Drainage Paper 56 gives the saturation pressure with the Tetens form:
- es = 0.6108 · exp(17.27 · T / (T + 237.3)) kPa
with T in °C, valid over the range this calculator uses (−40 to 60 °C). The vapour pressure is then e = es · RH/100 and the deficit is es − e. The constants are the ones printed in the paper, so the numbers match the reference tables used in irrigation and agronomy.
Worked example
At 25 °C:
- es = 0.6108 · exp(17.27 · 25 / 262.3) = 3.168 kPa
- at 60 % RH, e = 1.901 kPa and VPD = 3.168 − 1.901 = 1.267 kPa
- at 40 % RH, VPD = 1.901 kPa; at 90 % RH it is 0.317 kPa
At 30 °C and 50 % RH the same arithmetic gives es = 4.243 kPa and VPD = 2.121 kPa. Raising the temperature at constant relative humidity increases the VPD much faster than the relative humidity suggests, because es grows roughly 6–7 % per kelvin near room temperature.
VPD and relative humidity
Relative humidity says how full the air is relative to its own temperature; VPD says how much vapour pressure is missing. Two rooms at 25 °C/60 % and 30 °C/70 % have different VPDs even though both feel humid: the warmer room can hold more water, so its deficit is larger. That is why VPD is used to compare drying conditions across temperatures and why a control loop on VPD holds a different relative humidity at each setpoint.
Where it is used
- Greenhouses and growth rooms: VPD links transpiration to the air’s drying power; the setpoints are crop-specific.
- Drying and coating: the evaporation rate follows the vapour-pressure deficit, not the relative humidity alone.
- HVAC and clean rooms: a low VPD is the warning that condensation will form on a cold surface; the dew-point calculator gives that temperature directly.
- Compressed air and process gas: VPD is rarely quoted, but the same saturation curve underlies the absolute humidity calculator and the pressure dew point.
Common mistakes
Using VPD as a relative-humidity target. VPD is a pressure difference in kPa; a control system that needs %RH must convert it with the current temperature.
Assuming VPD is constant when air is heated. Heating at constant absolute humidity raises VPD sharply; the dew point and absolute humidity do not change.
Mixing formulas. FAO-56 uses 17.27/237.3; the WMO uses 17.62/243.12. Above freezing they agree within about 0.5 %, so a small difference between two tools is the formula, not a bug — check which one a datasheet used.
Ignoring the leaf or surface temperature. For a greenhouse, the relevant VPD often uses leaf temperature, not air temperature; the calculator gives the air value.
Frequently asked questions
Is VPD the same as relative humidity?
No. Relative humidity is a percentage of the saturation pressure at the same temperature; VPD is the difference between the saturation pressure and the actual vapour pressure, in kPa.
What is a good VPD?
It depends on the crop or process. The calculator gives the physical value; setpoints come from the crop or process specification, not from a universal number.
Does VPD change when air is heated?
Yes. At constant absolute humidity, heating lowers relative humidity and raises VPD steeply; the dew point stays the same.
Why does the number differ from a greenhouse controller?
Check the formula constants (FAO-56 against WMO), the temperature used (air or leaf) and the pressure. A few percent is normal; a large difference means a different input.