SensorCatalog

Absolute humidity calculator

Absolute humidity, mixing ratio and dew point from air temperature and relative humidity.

At 20 °C and 50 % relative humidity the absolute humidity is 8.62 g/m³ and the dew point 9.3 °C (WMO saturation curve); the same 50 % at 30 °C is 15.13 g/m³.

Air

Result

8.621g/m³

At 50 % RH

Mixing ratio
7.2427 g/kggrams of water per kg of dry air
Vapour pressure
11.66 hPasaturation 23.33 hPa
Dew point
9.3 °Cat the same vapour pressure
Valid range
-45 … 60 °CWMO saturation curve over water

Schematic

AHsat17.24 g/m³AH8.621 g/m³Relative humidity50 %0100 %
Drawn from the inputs above; not to scale.
Formulas and standards
e = RH/100 · ew(t)   AH = 1000 · e · 100 / (Rv · T)   x = 1000 · ε · e / (p − e)

The vapour pressure is the relative humidity times the saturation pressure at that temperature. Absolute humidity converts that vapour pressure into a mass per volume with the specific gas constant of water vapour (461.5 J/(kg·K)); the mixing ratio expresses the same water as grams per kilogram of dry air, so it also needs the total air pressure. The dew point is the temperature at which the same vapour pressure would saturate the air.

Saturation pressure over water after WMO-No. 8 (Sonntag 1990): 6.112·exp(17.62·t/(243.12 + t)) hPa, valid from −45 to 60 °C. The result is for pure water vapour; the enhancement factor of real air adds about 0.4 % at sea level and more at high pressure. The page’s dew-point calculator uses the same curve, so the two tools agree.

Looking for humidity sensors or transmitters?

Contact us

What absolute humidity is

Absolute humidity is the mass of water vapour in a cubic metre of air, in g/m³. It does not change when the air is heated or cooled as long as no water condenses: relative humidity changes, absolute humidity stays. That makes it the quantity to use when air is moved, mixed or dried in a plant, and relative humidity the quantity to use when condensation or comfort is the question.

The calculation

The vapour pressure e is the relative humidity times the saturation pressure at the air temperature:

  • e = RH/100 × ew(t)

Absolute humidity then follows from the gas law, with Rv = 461.5 J/(kg·K):

  • AH = 1000 × e × 100 / (Rv × (t + 273.15)) g/m³

The saturation pressure comes from the WMO-No. 8 curve over water, ew(t) = 6.112 × exp(17.62 t / (243.12 + t)) hPa, valid from −45 to 60 °C. The dew point is the temperature at which e becomes the saturation pressure; the calculator shows it because it is what a chilled-mirror instrument measures.

Worked example

Air at 20 °C and 50 % relative humidity:

  • ew(20) = 23.37 hPa, so e = 11.69 hPa
  • AH = 1000 × 11.69 × 100 / (461.5 × 293.15) = 8.62 g/m³
  • The dew point is 9.3 °C: cooling the air below that condenses water

At 30 °C and 50 % the same calculation gives 15.13 g/m³, and at 0 °C and 100 % it gives 4.85 g/m³. Cooling 20 °C air at 50 % to 10 °C raises the relative humidity to about 93 % without changing the absolute humidity; below 9.3 °C water starts to condense.

Mixing ratio and why pressure matters

The mixing ratio x is the mass of water per kilogram of dry air, in g/kg:

  • x = 1000 × ε × e / (p − e), with ε = 0.621981

It needs the total air pressure, and it is the quantity used in drying and combustion calculations because the dry-air mass is conserved when air is heated or leaks. At sea level and 20 °C/50 %, x is about 7.3 g/kg; at 900 hPa the same vapour pressure gives a larger mixing ratio.

Absolute vs relative humidity in a plant

A dryer removes water: absolute humidity falls, and the relative humidity falls with it. A heater only changes the temperature: absolute humidity stays, relative humidity drops, and the dew point stays. A humidifier adds water: both rise. When a sensor is selected or a duct is balanced, absolute humidity or mixing ratio describes the water actually present, and relative humidity describes the risk of condensation on a cold surface.

The dew-point calculator gives the same air in dew point, frost point and pressure dew point, and the HVAC and building automation notes show where these measurements are used.

Common mistakes

Reading relative humidity as absolute humidity. At 20 °C, 50 % RH is 8.62 g/m³; at 30 °C, 50 % RH is 15.13 g/m³. The same percentage is nearly twice the water.

Using the dry-bulb temperature for the dew point. The dew point is below the air temperature whenever the relative humidity is below 100 %, sometimes far below.

Ignoring pressure for the mixing ratio. Absolute humidity does not need the total pressure; the mixing ratio does, and a 10 % pressure error is a 10 % error in x.

Assuming the enhancement factor is negligible at high pressure. The curve is for pure water vapour; in compressed air the real-gas effect grows with pressure.

Frequently asked questions

What is absolute humidity in g/m³?

The mass of water vapour per cubic metre of air. At 20 °C and 50 % RH it is 8.62 g/m³.

How do I convert relative humidity to absolute humidity?

Multiply the relative humidity by the saturation pressure at the air temperature to get the vapour pressure, then convert with AH = 1000·e·100/(Rv·T).

Does absolute humidity change with temperature?

No, as long as no water condenses or evaporates. Heating air lowers the relative humidity and leaves the absolute humidity and dew point unchanged.

Why does the mixing ratio need pressure?

Because it is defined per kilogram of dry air, and the volume that holds a given mass of dry air depends on the total pressure.

Which range is valid?

The WMO curve over water is used from −45 to 60 °C. Below 0 °C the saturation curve over ice differs; the dew-point calculator handles frost.

↑ ↓ choose · Enter open · Esc close