SensorCatalog

Home › 4–20 mA scaling tables

4–20 mA to -1–1.5 bar: scaling table

A transmitter calibrated -1–1.5 bar: 4 mA = -1 bar, 20 mA = 1.5 bar. Linear output.

At a glance

Span
2.5 bar
Change per 1 mA
0.15625 bar
Change per 1 %
0.025 bar
Value at 12 mA
0.25 bar

Scaling table

Current (mA)Output (%)Value (bar)
4.000 %-1
6.0012.5 %-0.6875
8.0025 %-0.375
10.0037.5 %-0.0625
12.0050 %0.25
14.0062.5 %0.5625
16.0075 %0.875
18.0087.5 %1.1875
20.00100 %1.5

Open this range in the 4–20 mA converter

NAMUR NE 43 limits in bar

Current (mA)Value (bar)Meaning
3.6-1.0625Failure signal, downscale (≤ 3.6 mA)
3.8-1.03125Lower measuring limit (3.8 mA)
20.51.57813Upper measuring limit (20.5 mA)
21.01.65625Failure signal, upscale (≥ 21 mA)

Formula

PV = -1 + (I − 4) / 16 × 2.5 bar

Example: a reading of 13.6 mA corresponds to 0.5 bar. Going the other way, 0.875 bar corresponds to 16 mA.

Need a 4–20 mA pressure or level transmitter?

Request a quote at SensorSpan

↑ ↓ choose · Enter open · Esc close