What the heat load is
The heat load is the rate at which heat must be added to, or removed from, a flowing medium to change its temperature. It is the first number in sizing a heater, a chiller, a heat exchanger or a control valve for a temperature loop.
The equation
- P = ρ · Q · cp · ΔT / 3600 kW
Q is the volume flow in m³/h, ρ the density in kg/m³, cp the specific heat in kJ/(kg·K) and ΔT the temperature change in kelvin (the same number as °C). The 3600 converts hours to seconds and kJ/s to kW.
Worked example
1 m³/h of water, heated from 10 °C to 20 °C:
- P = 1000 × 1 × 4.186 × 10 / 3600 = 11.63 kW
- in other units: 11.63 kW = 10 000 kcal/h = 41.9 MJ/h
The same 1 m³/h of air at room temperature (ρ ≈ 1.2, cp ≈ 1.005) needs only 0.00335 kW, about 3.35 W, because there is very little mass in a cubic metre of air. That is why air heating is usually sized on mass flow or on the air handler’s duty, not on a water-style volume flow.
Sensible and latent heat
The equation covers sensible heat, the temperature change of a medium that does not change phase. Condensation, evaporation and chemical reaction add latent heat: water’s latent heat of vaporisation is about 2257 kJ/kg at 100 °C, so condensing 1 kg/h of steam releases about 0.63 kW. A steam heater needs the latent term; a water heater usually does not.
Where it is used
- Heater and chiller selection: the kW at the design flow and ΔT.
- Heat meters: the same product, integrated over time, gives kWh.
- Temperature control: the load sets the valve or heater capacity and the loop’s response time.
- Tank heating: the tank volume calculator gives the inventory, and the pipe velocity calculator checks the flow that carries the heat.
Common mistakes
Using the volume flow of a gas as if it were water. The density difference is a factor of about 800.
Forgetting the 3600. A result a thousand times too large is the usual symptom.
Using cp at the wrong temperature. cp changes with temperature, especially near a phase change.
Ignoring losses. The duty at the medium is not the duty at the heater terminals; insulation and pipe losses add.
Frequently asked questions
Is heat load the same as power?
For a steady flow with a known ΔT, yes: the heat load is the power the heater or chiller must deliver.
What is the unit?
kW is standard; 1 kW = 860 kcal/h = 3.6 MJ/h = 3412 BTU/h.
Can I use it for cooling?
Yes, with a negative ΔT; the magnitude is the cooling load.
Does it include the heat to warm the tank itself?
No. Warming the steel, the insulation and the pipe is a separate term that decays after start-up; add it for batch heating.
Why is air’s load so small?
Because its density and specific heat are low: a cubic metre of air carries about 1/800 of the heat of a cubic metre of water for the same ΔT.