The short answer
4–20 mA is the industrial standard for process transmitters, long cable runs and electrically noisy plants: loop current is identical at every point in the circuit, so cable resistance introduces zero measurement error as long as the power supply stays above the transmitter’s minimum voltage, and the 4 mA live zero instantly distinguishes a broken wire (0 mA) from a 0 % reading.
0–10 V is simpler and lower-power for short cable runs inside control cabinets, HVAC ducts, test benches and embedded electronics, and one voltage transmitter can feed several high-impedance receivers in parallel. Over long three-wire cables, however, supply current returning through the shared 0 V conductor shifts the voltage reference directly into the signal.
How cable resistance affects 4–20 mA vs 0–10 V
The table above compares both signals on the exact same 0.5 mm² copper cable (0.0344 Ω/m per conductor at 20 °C) from 10 m to 500 m.
In a two-wire 4–20 mA current loop, Kirchhoff’s current law forces the exact same current through the transmitter, the cable and the receiver’s 250 Ω input resistor. Cable resistance consumes voltage compliance, not measurement accuracy. At 300 m of 0.5 mm² copper (20.64 Ω round-trip) with a 24 V supply and a 250 Ω PLC input, the transmitter still sees 18.05 V at 22 mA alarm current — a comfortable +7.55 V margin above a 10.5 V minimum terminal voltage — and 0.00 % reading error. You can verify any supply, cable gauge and barrier drop with the loop power calculator.
In a three-wire 0–10 V transmitter, the power supply return and the analog signal reference share the same 0 V conductor. If the sensor draws 20 mA of operating current, that 20 mA creates a voltage drop ΔV = I · R_wire along the return wire that adds directly to the voltage measured at the PLC input:
- At 10 m (0.34 Ω return wire): +6.9 mV shift (0.07 % of 10 V span) — negligible.
- At 100 m (3.44 Ω return wire): +68.8 mV shift (0.69 % of span) — already larger than the reference accuracy of a 0.25 % or 0.5 % pressure transmitter.
- At 300 m (10.32 Ω return wire): +206.4 mV shift (2.06 % of span) — serious zero offset.
- At 500 m (17.20 Ω return wire): +344.0 mV shift (3.44 % of span).
Adding a fourth wire (separate signal ground from power 0 V) removes the supply-return shift, leaving only the tiny voltage-divider error between cable resistance and receiver input impedance (typically 100 kΩ to 1 MΩ). Even then, four conductors cost more than a two-wire 4–20 mA twisted pair. Check your exact 3-wire ground shift in the sensor supply voltage drop calculator.
Live zero and fault detection (NAMUR NE 43)
A 4–20 mA loop never sits at 0 mA during normal operation. Zero percent of the calibrated span is 4.0 mA (live zero), and 100 % is 20.0 mA. Under NAMUR NE 43, smart transmitters reserve currents outside 3.8 to 20.5 mA for diagnostics:
- ≤ 3.6 mA (including 0 mA from a cut cable, loose terminal or blown fuse): downscale fault.
- ≥ 21.0 mA: upscale fault (sensor burnout or electronics failure).
The PLC can therefore alarm immediately when a cable breaks or a transmitter loses power. Test any engineering range and fault threshold in the 4–20 mA converter.
A 0–10 V signal has a dead zero: 0.00 V can mean “the tank is empty”, “the duct pressure is zero”, “the cable was cut”, or “the 24 V fuse tripped”. Unless you switch to a live-zero voltage range such as 2–10 V or 1–5 V (which preserves a 20 % dead-band below zero), the controller cannot detect an open wire automatically.
Noise immunity in industrial environments
Industrial plants are full of variable-frequency drives (VFDs), contactors and motor cables that couple noise into adjacent signal wiring.
- 4–20 mA operates into a low receiver impedance (typically 250 Ω, converting 4–20 mA into 1–5 V inside the PLC card). Low loop impedance plus a twisted shielded pair makes capacitive electric-field pickup very small, and magnetic pickup cancels along the twist.
- 0–10 V terminates into a high input impedance (typically 100 kΩ to 1 MΩ) so the sensor does not load down. That high impedance allows coupled noise currents to develop much larger error voltages across the input terminals, and ground-potential differences between two cabinets inject directly into single-ended 0–10 V inputs.
Over a few metres inside a clean control cabinet, 0–10 V works well. Past 20 to 30 m through cable trays shared with power feeders, 4–20 mA is far more dependable.
Wiring, power consumption and multi-drop receivers
Each signal type has clear practical trade-offs in hardware and wiring:
- Two-wire loop power (4–20 mA): A two-wire transmitter powers its own electronics from the 4 mA baseline (for example 4 mA × 12 V ≈ 48 mW), needing only two conductors for both power and signal. Sensors that draw more power (radar, Coriolis, gas analysers) use four-wire active 4–20 mA outputs.
- Standby power and batteries (0–10 V): A continuous 4–20 mA loop draws at least 4 mA (and up to 20 mA) at all times, which drains batteries quickly and dissipates heat in dense multi-channel panels. A 0–10 V or ratiometric voltage sensor can draw under 1 mA — or wake up for a few milliseconds per reading — making voltage output much better suited to battery-powered loggers and embedded electronics.
- Feeding multiple devices: Because current is the same everywhere in series, one 4–20 mA loop can drive two devices (for example a local display and a PLC) in series as long as the total loop resistance stays within the supply voltage budget (typically ≤ 600 Ω at 24 V). One 0–10 V transmitter can drive several high-impedance inputs in parallel without adding voltage drops, provided ground loops are avoided.
- Digital communication (HART): 4–20 mA supports HART digital communication superimposed on the exact same two wires (requiring ≥ 250 Ω loop resistance), enabling remote calibration, diagnostics and secondary variables without extra cabling. 0–10 V carries no standard superimposed digital bus.
Converting between 4–20 mA and voltage inputs
Because a 250 Ω precision resistor converts 4–20 mA directly into 1–5 V (and 500 Ω converts it into 2–10 V), you can connect a 4–20 mA transmitter to a 0–10 V or 0–5 V PLC input simply by placing a precision 0.1 % shunt resistor across the voltage input terminals. Remember two checks when doing this:
- Verify that the extra 250 Ω or 500 Ω fits inside your 4–20 mA loop voltage budget with the loop power calculator.
- Check how much of the ADC’s full-scale range is actually used: converting 4–20 mA through 250 Ω onto a 0–10 V input uses only 1 to 5 V (40 % of the ADC span), costing more than 1.3 bits of effective resolution. Verify the code step size in the ADC resolution calculator.
When to choose 4–20 mA
- Process plants, water and wastewater, oil and gas, power generation and factory floors.
- Cable runs longer than 20 to 30 m or routed near VFDs, motors and AC power lines.
- Safety-relevant or unattended loops where broken-wire detection (NAMUR NE 43) is essential.
- Hazardous areas (intrinsic-safety barriers) and applications benefiting from two-wire power or HART diagnostics.
When to choose 0–10 V
- HVAC and building automation (VAV dampers, duct sensors, room transmitters) over short runs.
- Inside control cabinets, test rigs and OEM machines with short shielded wiring.
- Low-power or battery-operated systems where 4–20 mA quiescent current wastes too much energy.
- Sharing one sensor output across multiple high-impedance voltage inputs in parallel.
Common mistakes
Running a 3-wire 0–10 V sensor over 100+ metres of thin cable. Even 20 mA of sensor supply current returning on a shared 0.5 mm² ground wire adds +69 mV (+0.69 % of span) at 100 m and +206 mV (+2.06 %) at 300 m. Use 4–20 mA or a 4-wire differential input.
Assuming 0 V means zero flow or empty tank. On a 0–10 V input, a severed wire or unpowered sensor also reads 0 V. Use 4–20 mA or live-zero 2–10 V / 1–5 V whenever silent sensor loss is hazardous.
Putting two 4–20 mA inputs in parallel. Current splits unevenly between parallel loads and destroys both readings. Multiple 4–20 mA receivers must be wired in series, and only one receiver should ground the loop return unless a loop isolator is fitted.
Forgetting loop voltage compliance on a 500 Ω resistor. Converting 4–20 mA to 2–10 V with a 500 Ω resistor drops 11.0 V at 22 mA alarm current — leaving only 13.0 V from a 24 V supply before cable resistance. Always verify the margin at 22 mA, not 20 mA.
Frequently asked questions
Why is 4–20 mA better than 0–10 V for long distances?
In a 4–20 mA loop, the transmitter regulates current so the same milliamps flow through the entire series circuit regardless of wire resistance. Up to the power supply’s compliance limit (typically several hundred metres of copper cable at 24 V), wire resistance causes zero measurement error. In a 3-wire 0–10 V circuit, supply current returning through the shared 0 V conductor creates an IR voltage drop that directly offsets the reading.
How far can a 0–10 V signal travel without major error?
For a typical 3-wire 0–10 V sensor drawing 20 mA over 0.5 mm² copper cable, the shared 0 V return adds +0.07 % error at 10 m, +0.34 % at 50 m and +0.69 % at 100 m. In practice, keep 3-wire 0–10 V runs under 15 to 30 m (or use thicker cable or 4-wire differential sensing) and switch to 4–20 mA for longer runs.
Why does 4–20 mA start at 4 mA instead of 0 mA?
Starting at 4 mA provides two advantages: first, it creates a live zero so a broken wire or power loss (0 mA) is immediately distinguishable from a true 0 % measurement (4 mA); second, the 4 mA baseline supplies enough continuous current to power a two-wire transmitter without separate power conductors.
Can I convert a 4–20 mA signal to 0–10 V for a voltage PLC input?
You can convert 4–20 mA to 2–10 V using a precision 500 Ω resistor (or to 1–5 V using a 250 Ω resistor) across the voltage input terminals, then scale 2–10 V or 1–5 V in software. Always verify that the 24 V loop supply still has enough voltage margin at 22 mA with that resistor plus cable resistance in series.
Is 4–20 mA more resistant to electrical noise than 0–10 V?
Yes. A 4–20 mA receiver presents a low input resistance (typically 250 Ω) compared with 100 kΩ to 1 MΩ for a 0–10 V input. Induced capacitive noise currents produce far smaller error voltages across 250 Ω than across 100 kΩ, and differential loop currents reject ground potential differences between cabinets when properly isolated.
When is 0–10 V preferred over 4–20 mA?
0–10 V is preferred for short runs inside cabinets and HVAC/building-automation panels, low-power or battery-operated OEM instruments where a continuous 4–20 mA draw is unacceptable, and installations where one sensor needs to feed multiple high-impedance inputs in parallel.
Can a 4–20 mA transmitter be wired to two PLC inputs at once?
Yes, by wiring the two inputs in series (never in parallel), provided the combined input resistances plus cable resistance stay below the loop’s maximum allowable resistance at 22 mA, and at least one input is electrically isolated so you do not create a ground loop.