4–20 mA to 0–300 psi: scaling table

A transmitter calibrated 0–300 psi: 4 mA = 0 psi, 20 mA = 300 psi. Linear output.

At a glance

Span
300 psi
Change per 1 mA
18.75 psi
Change per 1 %
3 psi
Value at 12 mA
150 psi

Scaling table

Current (mA)Output (%)Value (psi)
4.000 %0
6.0012.5 %37.5
8.0025 %75
10.0037.5 %112.5
12.0050 %150
14.0062.5 %187.5
16.0075 %225
18.0087.5 %262.5
20.00100 %300

Open this range in the 4–20 mA converter

NAMUR NE 43 limits in psi

Current (mA)Value (psi)Meaning
3.6-7.5Failure signal, downscale (≤ 3.6 mA)
3.8-3.75Lower measuring limit (3.8 mA)
20.5309.375Upper measuring limit (20.5 mA)
21.0318.75Failure signal, upscale (≥ 21 mA)

Formula

PV = 0 + (I − 4) / 16 × 300 psi

Example: a reading of 13.6 mA corresponds to 180 psi. Going the other way, 225 psi corresponds to 16 mA.