SensorCatalog

Home › 4–20 mA scaling tables

4–20 mA to -1–0 bar: scaling table

A transmitter calibrated -1–0 bar: 4 mA = -1 bar, 20 mA = 0 bar. Linear output.

At a glance

Span
1 bar
Change per 1 mA
0.0625 bar
Change per 1 %
0.01 bar
Value at 12 mA
-0.5 bar

Scaling table

Current (mA)Output (%)Value (bar)
4.000 %-1
6.0012.5 %-0.875
8.0025 %-0.75
10.0037.5 %-0.625
12.0050 %-0.5
14.0062.5 %-0.375
16.0075 %-0.25
18.0087.5 %-0.125
20.00100 %0

Open this range in the 4–20 mA converter

NAMUR NE 43 limits in bar

Current (mA)Value (bar)Meaning
3.6-1.025Failure signal, downscale (≤ 3.6 mA)
3.8-1.0125Lower measuring limit (3.8 mA)
20.50.03125Upper measuring limit (20.5 mA)
21.00.0625Failure signal, upscale (≥ 21 mA)

Formula

PV = -1 + (I − 4) / 16 × 1 bar

Example: a reading of 13.6 mA corresponds to -0.4 bar. Going the other way, -0.25 bar corresponds to 16 mA.

Need a 4–20 mA pressure or level transmitter?

Request a quote at SensorSpan