Control valve Kv / Cv calculator

Required flow coefficient for a liquid: Kv and Cv from flow, differential pressure and specific gravity.

For 10 m³/h of water at 1 bar the required Kv is 10 and Cv is 11.56 (Cv = Kv/0.865); with only 0.25 bar available the Kv doubles to 20.

Duty

Result

10Kv

Cv = 11.56

Cv
11.5611 Cv = 0.865 Kv
Flow at 1 bar
10 m³/hwith this Kv, m³/h of water
Differential pressure
1 barSG 1
Scope
liquids only

Schematic

Flow10 m³/hΔp1 barKv10Cv11.561013.295Cv / Kv
Drawn from the inputs above; not to scale.
Formulas and standards
Kv = Q · √(SG / ΔP)   Cv = Kv / 0.865

Kv is the flow of water in m³/h at 1 bar differential pressure; Cv is the flow in US gpm at 1 psi. The two are linked exactly by their definitions, Cv = Kv/0.865, so a valve quoted in either unit can be compared. The calculation is for a liquid: the square-root relation between flow and pressure drop holds while the flow is turbulent and the valve is not choked.

Size the valve on the maximum flow with the minimum available pressure drop, not on the normal duty, and check the result against the valve’s own Cv table and travel. Gases and steam need the expansion factor and the critical-pressure-ratio equations from the valve standard or the maker’s sizing program; cavitation and flashing limit the usable ΔP and need P1, the vapour pressure and FL. A valve that is sized too large runs near its seat and controls poorly.

Looking for control valves or valve sizing support?

Contact us

What Kv and Cv mean

The flow coefficient describes how much liquid a valve passes for a given pressure drop. Kv is the flow in m³/h of water at 1 bar; Cv is the flow in US gallons per minute of water at 1 psi. Both are defined at the same reference conditions, so the two numbers are proportional:

  • Cv = Kv / 0.865

A valve with Kv = 10 passes 10 m³/h of water at 1 bar, which is Cv = 11.56. The calculator returns both, plus the flow the sized valve passes at 1 bar.

Sizing a liquid valve

For a liquid with specific gravity SG, flow Q and available differential pressure ΔP:

  • Kv = Q · √(SG / ΔP)

with Q in m³/h and ΔP in bar. Water at 20 °C has SG ≈ 0.998; a brine or a solvent has its own value. The relation assumes turbulent flow through the valve and no choking; both are normally true for water-like liquids at ordinary pressure drops.

Worked example

A line needs 10 m³/h of water and has 1 bar available across the valve:

  • Kv = 10 · √(1/1) = 10
  • Cv = 10/0.865 = 11.56

If only 0.25 bar is available, the required Kv doubles to 20: halving the pressure drop raises the coefficient by √2. If the liquid has SG 1.2 at 0.5 bar, Kv = 10·√(1.2/0.5) = 15.49.

Choosing the pressure drop

Size on the maximum flow with the minimum available differential pressure, not on the normal duty. A valve sized on normal flow will be wide open at the maximum and will have no control margin left; a valve sized with too little ΔP becomes impractically large. A common starting point is to take a substantial share of the system’s dynamic pressure drop at the valve, then check the result against the selected valve’s Cv table, its travel and its authority.

Cavitation, flashing and gases

The square-root relation assumes the liquid stays liquid. If the pressure at the vena contracta falls below the vapour pressure, the flow chokes and cavitates; if it stays below the vapour pressure downstream, it flashes. Both need P1, the vapour pressure and the valve’s recovery coefficient FL, and both limit the usable ΔP. Gases and steam use the expansion factor and a critical-pressure-ratio test instead of this liquid equation. For those duties use the valve manufacturer’s sizing program or the standard’s equations — the flow rate converter and pressure converter help with the units.

Common mistakes

Using gauge pressure for the pressure drop. ΔP is a difference, so gauge and absolute give the same number, but P1 for cavitation checks is absolute.

Sizing on normal flow. The valve must pass the maximum flow with the minimum ΔP; otherwise it cannot control at the extremes.

Confusing Cv and Kv. They differ by 15.6 %; a valve quoted as Cv 12 is Kv 10.4.

Ignoring the valve’s own table. The calculated Cv is the requirement; the selected valve’s actual Cv at the working travel is what the loop will see.

Frequently asked questions

Is Cv the same as Kv?

No. Cv is in US gpm at 1 psi, Kv in m³/h at 1 bar; Cv = Kv/0.865.

Which pressure drop should I use?

The minimum differential pressure available at the maximum flow, including the valve’s share of the system drop.

Can I use this for steam?

No. Steam and gases need the expansion factor and critical-flow checks; use the maker’s sizing data.

What is a good valve authority?

A common rule is that the valve should take a significant part of the system’s dynamic pressure drop, often around a third to a half; the exact target depends on the loop and the valve characteristic.

Why does a smaller Kv valve control better?

A valve that is oversized spends its travel near the seat, where small changes in position give large flow changes; a correctly sized valve uses more of its travel and controls more smoothly.