What Kv and Cv mean
The flow coefficient describes how much liquid a valve passes for a given pressure drop. Kv is the flow in m³/h of water at 1 bar; Cv is the flow in US gallons per minute of water at 1 psi. Both are defined at the same reference conditions, so the two numbers are proportional:
- Cv = Kv / 0.865
A valve with Kv = 10 passes 10 m³/h of water at 1 bar, which is Cv = 11.56. The calculator returns both, plus the flow the sized valve passes at 1 bar.
Sizing a liquid valve
For a liquid with specific gravity SG, flow Q and available differential pressure ΔP:
- Kv = Q · √(SG / ΔP)
with Q in m³/h and ΔP in bar. Water at 20 °C has SG ≈ 0.998; a brine or a solvent has its own value. The relation assumes turbulent flow through the valve and no choking; both are normally true for water-like liquids at ordinary pressure drops.
Worked example
A line needs 10 m³/h of water and has 1 bar available across the valve:
- Kv = 10 · √(1/1) = 10
- Cv = 10/0.865 = 11.56
If only 0.25 bar is available, the required Kv doubles to 20: halving the pressure drop raises the coefficient by √2. If the liquid has SG 1.2 at 0.5 bar, Kv = 10·√(1.2/0.5) = 15.49.
Choosing the pressure drop
Size on the maximum flow with the minimum available differential pressure, not on the normal duty. A valve sized on normal flow will be wide open at the maximum and will have no control margin left; a valve sized with too little ΔP becomes impractically large. A common starting point is to take a substantial share of the system’s dynamic pressure drop at the valve, then check the result against the selected valve’s Cv table, its travel and its authority.
Cavitation, flashing and gases
The square-root relation assumes the liquid stays liquid. If the pressure at the vena contracta falls below the vapour pressure, the flow chokes and cavitates; if it stays below the vapour pressure downstream, it flashes. Both need P1, the vapour pressure and the valve’s recovery coefficient FL, and both limit the usable ΔP. Gases and steam use the expansion factor and a critical-pressure-ratio test instead of this liquid equation. For those duties use the valve manufacturer’s sizing program or the standard’s equations — the flow rate converter and pressure converter help with the units.
Common mistakes
Using gauge pressure for the pressure drop. ΔP is a difference, so gauge and absolute give the same number, but P1 for cavitation checks is absolute.
Sizing on normal flow. The valve must pass the maximum flow with the minimum ΔP; otherwise it cannot control at the extremes.
Confusing Cv and Kv. They differ by 15.6 %; a valve quoted as Cv 12 is Kv 10.4.
Ignoring the valve’s own table. The calculated Cv is the requirement; the selected valve’s actual Cv at the working travel is what the loop will see.
Frequently asked questions
Is Cv the same as Kv?
No. Cv is in US gpm at 1 psi, Kv in m³/h at 1 bar; Cv = Kv/0.865.
Which pressure drop should I use?
The minimum differential pressure available at the maximum flow, including the valve’s share of the system drop.
Can I use this for steam?
No. Steam and gases need the expansion factor and critical-flow checks; use the maker’s sizing data.
What is a good valve authority?
A common rule is that the valve should take a significant part of the system’s dynamic pressure drop, often around a third to a half; the exact target depends on the loop and the valve characteristic.
Why does a smaller Kv valve control better?
A valve that is oversized spends its travel near the seat, where small changes in position give large flow changes; a correctly sized valve uses more of its travel and controls more smoothly.