4–20 mA to 0–200 °C: scaling table

A transmitter calibrated 0–200 °C: 4 mA = 0 °C, 20 mA = 200 °C. Linear output.

At a glance

Span
200 °C
Change per 1 mA
12.5 °C
Change per 1 %
2 °C
Value at 12 mA
100 °C

Scaling table

Current (mA)Output (%)Value (°C)
4.000 %0
6.0012.5 %25
8.0025 %50
10.0037.5 %75
12.0050 %100
14.0062.5 %125
16.0075 %150
18.0087.5 %175
20.00100 %200

Open this range in the 4–20 mA converter

NAMUR NE 43 limits in °C

Current (mA)Value (°C)Meaning
3.6-5Failure signal, downscale (≤ 3.6 mA)
3.8-2.5Lower measuring limit (3.8 mA)
20.5206.25Upper measuring limit (20.5 mA)
21.0212.5Failure signal, upscale (≥ 21 mA)

Formula

PV = 0 + (I − 4) / 16 × 200 °C

Example: a reading of 13.6 mA corresponds to 120 °C. Going the other way, 150 °C corresponds to 16 mA.