How the 4–20 mA converter works
A 4–20 mA transmitter maps its calibrated range linearly onto a loop current: the lower range value (LRV) at 4 mA and the upper range value (URV) at 20 mA. The live zero at 4 mA lets the receiver tell a genuine zero reading from a broken wire, and it powers two-wire transmitters from the loop itself.
For a linear output:
PV = LRV + (I − 4) / 16 × (URV − LRV)
The converter links three fields: loop current, percent of span and process value. Type in any of them and the other two follow. There is no mode switch; the field you edited last is the input.
Worked example
A pressure transmitter is calibrated 0 to 10 bar. At 12 mA:
- (12 − 4) / 16 = 0.5, so the output is 50 %
- PV = 0 + 0.5 × 10 = 5 bar
- Each milliamp is worth 10 / 16 = 0.625 bar
- Across a 250 Ω resistor, 12 mA gives 3.000 V: the classic 1–5 V input
The scaling table lists the five standard check points (4, 8, 12, 16 and 20 mA) for your range. Click any row to load it into the converter.
Square-root output for flow
Differential-pressure flowmeters produce a pressure difference proportional to the square of flow. Apply the following square-root extraction only when the incoming current is linear in differential pressure. If the transmitter already extracts the square root internally, its current is linear in flow: select “Linear” here to avoid extracting the square root twice.
PV = LRV + √((I − 4) / 16) × (URV − LRV)
With a 0–100 range and square-root output, 12 mA is not 50 but 70.71, and 8 mA (25 % of current span) already represents 50 % of flow. Select “Square root (flow)” in the Output field to apply this. Below 4 mA a square-root output has no defined flow value, and the calculator says so instead of returning a number.
NAMUR NE 43 signal states
NAMUR recommendation NE 43 standardises how the current signals faults, so a control system can tell a measurement from a failure:
| Current | Meaning |
|---|---|
| ≤ 3.6 mA | Failure signal (downscale) |
| 3.6 to 3.8 mA | Below the measuring limit |
| 3.8 to 4 mA | Under range, still a valid measurement |
| 4 to 20 mA | Normal range |
| 20 to 20.5 mA | Over range, still valid |
| 20.5 to 21 mA | Above the measuring limit |
| ≥ 21 mA | Failure signal (upscale) |
The scale under the converter shows these zones. You can drag the marker, or focus it and use the arrow keys, to see how any current is classified. Configure your control system alarms to the same limits as the transmitter.
Finding the range from two readings
If the calibration is unknown, the range finder works it out from two known points. Enter two readings, each a current and the value it represents, and it extrapolates the values at 4 and 20 mA. Example: 7.2 mA at 2 bar and 16.8 mA at 8 bar give a range of 0 to 10 bar. “Apply this range to the transmitter” copies the result to the range fields above. This assumes a linear output; it cannot recover a square-root characteristic.
Common mistakes
Assuming 0 mA is zero. A dead loop reads 0 mA, which is outside the valid range, not the bottom of the scale. Receivers should treat it as a fault.
Applying the square root twice. For current linear in differential pressure, 8 mA is 25 % differential pressure and 50 % flow. For a transmitter that already outputs flow after internal extraction, 8 mA is 25 % flow; select “Linear”.
Forgetting the HART resistor. HART communication needs a loop resistance of typically at least 250 Ω. Check the voltage budget with the loop power calculator.
Mismatched ranges. If the transmitter is re-ranged in the field but the control system isn’t, every reading is wrong in proportion. Copy the result from this tool and keep it with the loop documentation.
Frequently asked questions
Why 4 mA instead of 0 mA?
The live zero distinguishes a real zero reading from an open circuit, and the 4 mA minimum supplies enough power for a two-wire transmitter to operate.
What is the resolution of a 4–20 mA signal?
The analog signal itself is continuous. Resolution is set by the receiver’s A/D converter and noise; a 16-bit input card resolves the 16 mA span to a few hundred nanoamps.
Can the converter handle reverse-acting ranges?
Yes. Enter a value at 4 mA that is higher than the value at 20 mA, for example 100 to 0, and the conversion works the same way.
Does it work for 0–20 mA signals?
Yes. Choose 0–20 mA in the Signal field; 0–10 V, 2–10 V, 0–5 V and 1–5 V are there too. The NAMUR NE 43 states apply only to 4–20 mA. A signal that starts at 0 has no live zero, so a broken wire looks like the bottom of the range and cannot be flagged.