RTD lead-wire error calculator

How much cable resistance adds to a PT100 or PT1000 reading with 2-, 3- or 4-wire connection.

In a two-wire PT100 circuit both leads add to the reading: 10 m of 0.5 mm² copper adds 0.69 Ω, about +1.8 °C at 0 °C. A three-wire circuit cancels it when the leads match.

Sensor

Element
Connection

Cable

Result

+1.814°C error, 2-wire

Over your ±0.5 °C budget.

Resistance per conductor
0.344 Ω10 m, 0.5 mm² copper, 20 °C
Element sensitivity
0.3793 Ω/°CPT100 at 100 °C
2-wire error
+1.814 °C0.688 Ω added
3-wire error
+0.045 °C5 % lead mismatch
4-wire error
≈ 0leads not in the measurement
Maximum cable length
2.756 m2-wire, ±0.5 °C budget
Class A tolerance
±0.35 °Celement alone, IEC 60751
Class B tolerance
±0.80 °Celement alone, IEC 60751

Schematic

Measuring inputΩ10 m · 0.5 mm²0.344 Ω per conductorPT100138.506 Ω100 °C
Drawn from the inputs above; not to scale.
Formulas and standards
Rlead = ρ × L / A,   error = T(R(t) + ΔR) − t
ρ = 0.0172 Ω·mm²/m × (1 + 0.00393 × (Tcable − 20 °C))

2-wire: both leads add to the element, ΔR = 2 Rlead. 3-wire: the instrument cancels the leads assuming they are equal, so only the mismatch remains, ΔR ≈ Rlead × mismatch. 4-wire: current and voltage use separate leads, so lead resistance does not enter the measurement.

The full IEC 60751 curve is inverted; ΔR/(dR/dt) is only a local approximation. Two-wire error is positive; three-wire mismatch can have either sign, and the larger positive magnitude is shown. Cable-length limits also respect the IEC temperature range. Copper resistance rises about 0.39 % per °C; the cable resistance here is at 20 °C.

Need 3- or 4-wire PT100 assemblies or head-mount RTD transmitters?

Contact us

How lead resistance turns into temperature error

An RTD measures temperature through its resistance, so any resistance in the connecting cable looks like extra temperature. The calculator works out the resistance of each conductor from length, cross-section and the resistivity of copper (0.0172 Ω·mm²/m at 20 °C). It then adds the lead resistance to the element resistance and inverts the complete IEC 60751 curve. Dividing by the local sensitivity is only an approximation, especially for long cables.

How much of the lead resistance reaches the measurement depends on the connection:

  • 2-wire: the measuring current flows through both leads, so the instrument sees the element plus twice the lead resistance. ΔR = 2 × Rlead.
  • 3-wire: a third lead lets the instrument measure the lead resistance and subtract it, assuming all leads are equal. What remains is the difference between the leads. ΔR ≈ Rlead × mismatch.
  • 4-wire: current flows through one pair and voltage is sensed through the other, which carries virtually no current. Lead resistance drops out of the measurement.

Worked example

A PT100 at 100 °C is connected with 10 m of 0.5 mm² copper cable.

  • Resistance per conductor: 0.0172 × 10 / 0.5 = 0.344 Ω
  • Element sensitivity at 100 °C: 0.3793 Ω/°C
  • 2-wire: 2 × 0.344 = 0.688 Ω, so the reading is 1.814 °C high
  • 3-wire with 5 % mismatch between the leads: 0.344 × 0.05 = 0.0172 Ω, an error of 0.045 °C
  • 4-wire: effectively zero

The 2-wire error alone is more than five times the class A tolerance of the element at that temperature (±0.35 °C). For a ±0.5 °C error budget, the longest 2-wire cable would be 2.76 m.

Choosing the connection

2-wire 3-wire 4-wire
Lead error Full (both leads) Only the mismatch Negligible
Typical use Short leads, PT1000, low accuracy Industrial standard for PT100 Laboratory, calibration, long runs
Instrument support Universal Almost all RTD inputs Most transmitters, fewer PLC cards

The calculator suggests the fewest wires that keep the error inside your budget; that is also the specification passed to product matching.

Ways to reduce the error

  • Use a PT1000. For small lead errors, the error in degrees is approximately ten times smaller for the same cable, because the element’s sensitivity is ten times larger.
  • Thicker conductors. Lead resistance is inversely proportional to cross-section.
  • Mount a transmitter at the sensor. A head-mount transmitter converts the reading to 4–20 mA within centimetres of the element; the long cable then carries a current signal that isn’t affected by its resistance.
  • Keep 3-wire leads identical. Use the same cable for all three cores, with no extra terminals or splices in only one lead.

Common mistakes

Assuming 3-wire cancels everything. Compensation is only as good as the lead match. Terminal resistance, corroded connections or a joint in one core all add mismatch.

Forgetting temperature of the cable. Copper resistance rises about 0.39 % per °C. A cable running through a hot area adds more resistance than the 20 °C figure.

Measuring a 2-wire sensor with a multimeter and trusting the reading. The meter includes both leads. Short the leads at the sensor end, measure, and subtract.

Frequently asked questions

Does lead resistance make the reading high or low?

With two wires, the reading is high. A three-wire mismatch can make it high or low, depending on which lead has more resistance. The calculator reports the larger positive magnitude for the stated mismatch.

How do I enter AWG wire?

Select the AWG size in the conductor field; the cross-section in mm² is shown next to it.

Can I use this for nickel or copper RTDs?

No. The sensitivity is calculated from the platinum IEC 60751 curve. For other materials the method is the same, but the sensitivity differs.

Where do I convert resistance to temperature?

Use the PT100 / PT1000 calculator, or the PT100 resistance table for a printed reference.