SensorCatalog

Home › 4–20 mA scaling tables

4–20 mA to 0–25 bar: scaling table

A transmitter calibrated 0–25 bar: 4 mA = 0 bar, 20 mA = 25 bar. Linear output.

At a glance

Span
25 bar
Change per 1 mA
1.5625 bar
Change per 1 %
0.25 bar
Value at 12 mA
12.5 bar

Scaling table

Current (mA)Output (%)Value (bar)
4.000 %0
6.0012.5 %3.125
8.0025 %6.25
10.0037.5 %9.375
12.0050 %12.5
14.0062.5 %15.625
16.0075 %18.75
18.0087.5 %21.875
20.00100 %25

Open this range in the 4–20 mA converter

NAMUR NE 43 limits in bar

Current (mA)Value (bar)Meaning
3.6-0.625Failure signal, downscale (≤ 3.6 mA)
3.8-0.3125Lower measuring limit (3.8 mA)
20.525.7813Upper measuring limit (20.5 mA)
21.026.5625Failure signal, upscale (≥ 21 mA)

Formula

PV = 0 + (I − 4) / 16 × 25 bar

Example: a reading of 13.6 mA corresponds to 15 bar. Going the other way, 18.75 bar corresponds to 16 mA.

Need a 4–20 mA pressure or level transmitter?

Request a quote at SensorSpan