4–20 mA to 0–6 bar: scaling table

A transmitter calibrated 0–6 bar: 4 mA = 0 bar, 20 mA = 6 bar. Linear output.

At a glance

Span
6 bar
Change per 1 mA
0.375 bar
Change per 1 %
0.06 bar
Value at 12 mA
3 bar

Scaling table

Current (mA)Output (%)Value (bar)
4.000 %0
6.0012.5 %0.75
8.0025 %1.5
10.0037.5 %2.25
12.0050 %3
14.0062.5 %3.75
16.0075 %4.5
18.0087.5 %5.25
20.00100 %6

Open this range in the 4–20 mA converter

NAMUR NE 43 limits in bar

Current (mA)Value (bar)Meaning
3.6-0.15Failure signal, downscale (≤ 3.6 mA)
3.8-0.075Lower measuring limit (3.8 mA)
20.56.1875Upper measuring limit (20.5 mA)
21.06.375Failure signal, upscale (≥ 21 mA)

Formula

PV = 0 + (I − 4) / 16 × 6 bar

Example: a reading of 13.6 mA corresponds to 3.6 bar. Going the other way, 4.5 bar corresponds to 16 mA.