Baud rate vs. cable length under TIA/EIA-485-A
RS-485 is a differential twisted-pair physical layer designed for noisy plant floors. At low speeds (up to 100 kbps), DC copper resistance limits a standard 24 AWG (120 Ω) bus to 1,200 m (4,000 ft). Above 100 kbps, skin effect and cable capacitance roll off the usable distance roughly inversely with baud rate:
| Protocol / speed | Baud rate | Max trunk length | Max stub length |
|---|---|---|---|
| Modbus RTU (long haul) | 9,600 bps | 1,200 m | 20 m |
| Modbus RTU (default) | 19,200 bps | 1,200 m | 20 m |
| BACnet MS/TP | 76,800 bps | 1,200 m | 12.9 m |
| High-speed Modbus RTU | 115,200 bps | 1,042 m | 8.6 m |
| DMX512 | 250 kbps | 480 m | 4.0 m |
| Fast industrial bus | 1 Mbps | 120 m | 1.0 m |
| Maximum TIA-485-A | 10 Mbps | 12 m | 0.1 m |
Once the bus is wired and frames are arriving cleanly, decode register payloads and byte order with the Modbus register decoder. If the bus cable also carries DC power to field sensors, check wire sizing with the sensor supply voltage drop calculator.
Unit loads, termination and daisy-chain wiring
Unit loads (UL): TIA/EIA-485-A defines 1 Unit Load as an input impedance of at least 12 kΩ and allows up to 32 UL per bus segment. Legacy 1 UL transceivers (such as the classic SN75176) cap a segment at 32 devices. Modern 1/4 UL (48 kΩ) and 1/8 UL (96 kΩ) transceivers allow 128 or 256 nodes on one daisy chain without a repeater.
Termination: Match the cable characteristic impedance (normally 120 Ω for RS-485 twisted pair, 100 Ω for Cat5e, or 150 Ω for PROFIBUS DP) with one resistor at each physical end of the trunk. Never install termination resistors on intermediate nodes, because three 120 Ω resistors in parallel drop the load to 40 Ω and overload the driver below its 54 Ω minimum rating.
Topology: Always wire RS-485 as a single daisy chain with short drop stubs. Star or tree wiring creates multiple impedance discontinuities and reflections that corrupt frames even at moderate baud rates.
Fail-safe biasing resistors (pull-up / pull-down)
When no node is transmitting, every driver releases the bus into high impedance. Without biasing, the differential voltage across the 60 Ω parallel termination collapses to 0 V — inside the ±200 mV indeterminate region of legacy RS-485 receivers — where electrical noise can trigger framing errors or phantom bytes.
Connecting a pull-up resistor RB from B (+) to Vcc and an equal pull-down resistor RB from A (−) to GND at one end of the bus (usually at the master/PLC) holds the idle voltage above +200 mV. For a 5 V supply on a doubly terminated 120 Ω bus with 16 × 1 UL nodes, 620 Ω standard E24 resistors hold the idle bus at about 214 mV while drawing less than 4 mA. On 3.3 V buses, external biasing requires heavier resistors (~390 Ω); prefer modern true fail-safe transceivers (−50 mV to −200 mV threshold) instead.
Frequently asked questions
Why are two 120 Ω termination resistors used on RS-485?
A standard RS-485 twisted-pair cable has a characteristic impedance of 120 Ω. Placing one 120 Ω resistor at each physical end absorbs the signal wave in both directions and prevents reflections, while keeping the DC parallel load (60 Ω) above the 54 Ω minimum driver specification.
Can I run RS-485 over Cat5e or Cat6 Ethernet cable?
Yes, over moderate distances. Cat5e/Cat6 twisted pair has a nominal characteristic impedance of 100 Ω (not 120 Ω), so match both end terminators to 100 Ω and keep total unit loads well below 32 UL so the combined bus load stays safely above 50 Ω.
Should the cable shield be grounded at both ends?
Ground the shield to protective earth at one end only (typically the control cabinet) to avoid 50/60 Hz ground loops. Always run a third signal-reference conductor (GND / Common) between RS-485 devices so common-mode voltage stays within the −7 V to +12 V TIA/EIA-485-A window.
Do I need fail-safe bias resistors on every node?
No. Install fail-safe pull-up and pull-down resistors at one point only on the bus — typically inside the master PLC or gateway. Enabling bias switches on multiple nodes puts the resistors in parallel and overloads the bus drivers.