4–20 mA to 0–1 bar: scaling table

A transmitter calibrated 0–1 bar: 4 mA = 0 bar, 20 mA = 1 bar. Linear output.

At a glance

Span
1 bar
Change per 1 mA
0.0625 bar
Change per 1 %
0.01 bar
Value at 12 mA
0.5 bar

Scaling table

Current (mA)Output (%)Value (bar)
4.000 %0
6.0012.5 %0.125
8.0025 %0.25
10.0037.5 %0.375
12.0050 %0.5
14.0062.5 %0.625
16.0075 %0.75
18.0087.5 %0.875
20.00100 %1

Open this range in the 4–20 mA converter

NAMUR NE 43 limits in bar

Current (mA)Value (bar)Meaning
3.6-0.025Failure signal, downscale (≤ 3.6 mA)
3.8-0.0125Lower measuring limit (3.8 mA)
20.51.03125Upper measuring limit (20.5 mA)
21.01.0625Failure signal, upscale (≥ 21 mA)

Formula

PV = 0 + (I − 4) / 16 × 1 bar

Example: a reading of 13.6 mA corresponds to 0.6 bar. Going the other way, 0.75 bar corresponds to 16 mA.