How the PT1000 calculator works
A PT1000 is a platinum resistance thermometer with 1000 Ω at 0 °C. It follows the same Callendar–Van Dusen curve as a PT100, per IEC 60751, with α = 0.00385:
- Above 0 °C: R(t) = 1000 × (1 + A·t + B·t²)
- Below 0 °C: R(t) = 1000 × (1 + A·t + B·t² + C·(t − 100)·t³), with A = 3.9083 × 10⁻³, B = −5.775 × 10⁻⁷ and C = −4.183 × 10⁻¹²
The calculator converts in both directions. Type a temperature to get the resistance, or a resistance to get the temperature; the last field you edit is the input. Resistance to temperature is solved by the same inverse function as the PT100 calculator, not by a lookup table, so the answer is exact for the IEC curve to better than 10⁻⁶ °C.
The valid range is −200 to 850 °C, the range IEC 60751 defines for platinum elements. Outside it the calculator says so instead of returning a made-up number.
Worked examples
- 0 °C → 1000.000 Ω
- 100 °C → 1385.055 Ω, usually shown as 1385.06 Ω
- −50 °C → 803.063 Ω
- 200 °C → 1758.560 Ω
- 850 °C → 3904.811 Ω
In reverse, 1385.055 Ω returns 100 °C. Each degree near room temperature changes the resistance by about 3.9 Ω, which is why a two-wire PT1000 tolerates cable resistance far better than a PT100.
PT1000 vs PT100: same curve, ten times the resistance
Both elements are platinum and both use α = 0.00385. The PT1000 is exactly ten times the resistance at every temperature, so its sensitivity is also ten times higher: 3.9083 Ω/°C at 0 °C against 0.39083 Ω/°C for the PT100.
That matters for lead resistance. A 10 m run of 0.5 mm² copper has about 0.344 Ω per conductor at 20 °C, so a two-wire loop adds 0.688 Ω. On a PT1000 at 100 °C that is 0.688 / 3.7928 ≈ 0.18 °C of error. On a PT100 at the same temperature it is 0.688 / 0.37928 ≈ 1.81 °C, ten times worse. The RTD lead-wire error calculator compares 2-, 3- and 4-wire connection for both elements.
The comparison is not all in the PT1000’s favour: for the same current it dissipates ten times the power (P = I²R), so self-heating is the thing to watch in still air. Many transmitters therefore excite a PT1000 with a smaller current than a PT100, and the temperature rise must be read from the probe datasheet, not guessed.
Where the PT1000 is the better choice
- Long cable runs and two-wire connections, where the higher resistance swamps the lead resistance.
- Thin-film elements in small probes and surface sensors, where a sturdy 100 Ω wire-wound element does not fit.
- Battery, EV and electronics work, where the higher signal suits low-power ADCs and simple dividers.
- Applications where the same transmitter must accept both elements: PT1000 reaches the same resolution with less current.
A PT100 remains the better choice where the extra resistance makes matching harder, or where the installed base and spares are PT100. At the same tolerance class, the two elements have the same accuracy in °C; only the wiring error and the self-heating change.
Wiring and self-heating
A two-wire connection puts both leads in series with the element; a three-wire connection subtracts one lead if all three are equal; a four-wire connection keeps the current loop separate from the voltage sense and removes lead resistance almost completely. Above a few metres, three- or four-wire is the safe choice even with a PT1000.
Self-heating is the product of the current squared and the element resistance. At 1 mA a PT1000 at 100 °C dissipates about 1.4 mW. The temperature rise per milliwatt is a property of the probe (its dissipation coefficient), so check the datasheet; in a small thin-film sensor it can be a few tenths of a kelvin per milliwatt.
Tolerance classes
IEC 60751 defines the tolerance classes by a fixed term plus a slope term:
- Class AA: ±(0.10 + 0.0017 × |t|) °C
- Class A: ±(0.15 + 0.002 × |t|) °C
- Class B: ±(0.30 + 0.005 × |t|) °C
- Class C: ±(0.6 + 0.01 × |t|) °C
At 100 °C, class A allows ±0.35 °C, which is ±1.33 Ω on a PT1000. The range over which each class is defined depends on wire-wound or thin-film construction; the calculator shows the wire-wound limits and the datasheet decides the rest.
Common mistakes
Assuming a PT1000 is ten times more accurate. It is not. The tolerance is specified in °C and is the same as the PT100 of the same class. What improves is the lead-resistance error.
Reading a PT100 table for a PT1000. Every value is ten times larger. Use the PT1000 resistance table or the calculator, and check the column heading before writing a value into a transmitter.
Using two wires on a long run. A PT1000 hides the error better, but it does not remove it. Above a few metres, use three or four wires.
Ignoring self-heating. The higher resistance makes the same excitation current dissipate more power. If the probe sits in still air, compare the datasheet’s dissipation coefficient with the power the transmitter delivers.
Expecting a linear output. The curve is close to linear near room temperature, but it is not a straight line; at 850 °C the sensitivity has fallen to about 3.2 Ω/°C. Use the curve, not a single slope.
Frequently asked questions
Is a PT1000 more accurate than a PT100?
At the same tolerance class, no: both are specified to the same ±°C limits. The PT1000 is more accurate in a two-wire circuit because its higher resistance makes the lead error ten times smaller.
What is the resistance of a PT1000 at 100 °C?
1385.055 Ω per IEC 60751 (α = 0.00385). The calculator and the reference table show 1385.06 Ω when rounded to two decimals.
Can I use a PT1000 with a PT100 transmitter?
Only if the transmitter can be configured for 1000 Ω. Many temperature transmitters and PLC cards accept both, but the input type must be set correctly; a PT1000 read as a PT100 shows a large negative error.
Why is the PT1000 preferred for long cables?
Because its sensitivity is ten times higher, the same lead resistance produces a tenth of the temperature error. A three-wire connection removes most of the remainder.
How much current should excite a PT1000?
As little as the transmitter allows while keeping a usable signal. 0.1 to 1 mA is typical; at 1 mA the element dissipates about 1 mW at 100 °C, and the resulting rise depends on the probe.
Does the calculator work below 0 °C?
Yes, down to −200 °C. The C coefficient is applied below 0 °C exactly as IEC 60751 defines it.
Which tolerance class should I order?
Class A or AA for process and laboratory measurements, class B for general monitoring. Check the temperature range over which the class is defined, and the construction of the element.