4–20 mA to 0–2.5 bar: scaling table

A transmitter calibrated 0–2.5 bar: 4 mA = 0 bar, 20 mA = 2.5 bar. Linear output.

At a glance

Span
2.5 bar
Change per 1 mA
0.15625 bar
Change per 1 %
0.025 bar
Value at 12 mA
1.25 bar

Scaling table

Current (mA)Output (%)Value (bar)
4.000 %0
6.0012.5 %0.3125
8.0025 %0.625
10.0037.5 %0.9375
12.0050 %1.25
14.0062.5 %1.5625
16.0075 %1.875
18.0087.5 %2.1875
20.00100 %2.5

Open this range in the 4–20 mA converter

NAMUR NE 43 limits in bar

Current (mA)Value (bar)Meaning
3.6-0.0625Failure signal, downscale (≤ 3.6 mA)
3.8-0.03125Lower measuring limit (3.8 mA)
20.52.57813Upper measuring limit (20.5 mA)
21.02.65625Failure signal, upscale (≥ 21 mA)

Formula

PV = 0 + (I − 4) / 16 × 2.5 bar

Example: a reading of 13.6 mA corresponds to 1.5 bar. Going the other way, 1.875 bar corresponds to 16 mA.