SensorCatalog

Home › 4–20 mA scaling tables

4–20 mA to 0–40 bar: scaling table

A transmitter calibrated 0–40 bar: 4 mA = 0 bar, 20 mA = 40 bar. Linear output.

At a glance

Span
40 bar
Change per 1 mA
2.5 bar
Change per 1 %
0.4 bar
Value at 12 mA
20 bar

Scaling table

Current (mA)Output (%)Value (bar)
4.000 %0
6.0012.5 %5
8.0025 %10
10.0037.5 %15
12.0050 %20
14.0062.5 %25
16.0075 %30
18.0087.5 %35
20.00100 %40

Open this range in the 4–20 mA converter

NAMUR NE 43 limits in bar

Current (mA)Value (bar)Meaning
3.6-1Failure signal, downscale (≤ 3.6 mA)
3.8-0.5Lower measuring limit (3.8 mA)
20.541.25Upper measuring limit (20.5 mA)
21.042.5Failure signal, upscale (≥ 21 mA)

Formula

PV = 0 + (I − 4) / 16 × 40 bar

Example: a reading of 13.6 mA corresponds to 24 bar. Going the other way, 30 bar corresponds to 16 mA.

Need a 4–20 mA pressure or level transmitter?

Request a quote at SensorSpan

↑ ↓ choose · Enter open · Esc close