SensorCatalog

Glossary of sensor and instrumentation terms

Short definitions of the terms used across the calculators, with links to the tool where each one matters.

Signals and loops

4–20 mA

The standard analog current signal for process transmitters: 4 mA at the lower range value, 20 mA at the upper. The live zero at 4 mA tells a real zero from a broken wire and leaves enough current to power a two-wire transmitter. See the 4–20 mA converter.

Live zero

A signal whose zero is not zero current or voltage, such as 4 mA in a 4–20 mA loop. A dead loop (0 mA) is therefore recognisable as a fault.

LRV and URV

Lower and upper range value: the process values a transmitter is calibrated to at 4 mA and 20 mA. The difference between them is the span.

NAMUR NE 43

A NAMUR recommendation that defines how a 4–20 mA signal reports failures: currents up to 3.6 mA and from 21 mA signal a fault, 3.8 to 20.5 mA is a valid measurement including slight under- and over-range.

HART

A digital protocol superimposed on the 4–20 mA current as a small frequency-shift signal. It needs a loop resistance of typically at least 250 Ω for the handheld or modem to read the signal.

Two-wire transmitter

A transmitter powered by the loop it signals on. It needs a minimum terminal voltage at the highest loop current; the loop power calculator checks the budget.

Load resistance (burden)

The total series resistance in a current loop: input resistors, barriers and the cable. Every ohm takes voltage away from the transmitter.

Square-root output

A transmitter output proportional to the square root of the measured differential pressure, used for flow measurement with orifice plates and similar primary elements.

Temperature

RTD

Resistance temperature detector: a sensor whose resistance rises with temperature, usually platinum. See the PT100 / PT1000 calculator.

PT100 and PT1000

Platinum RTDs with 100 Ω and 1000 Ω at 0 °C. Both follow the same IEC 60751 curve; a PT1000 is less affected by lead resistance and self-heating.

Callendar–Van Dusen equation

The equation IEC 60751 uses for the resistance of an industrial platinum RTD: R(t) = R₀ [1 + A·t + B·t² + C·(t − 100)·t³], with the C term only below 0 °C.

Tolerance class (IEC 60751)

The permitted deviation of an RTD element from the standard curve: class AA ±(0.10 + 0.0017·|t|) °C, A ±(0.15 + 0.002·|t|) °C, B ±(0.30 + 0.005·|t|) °C.

2-, 3- and 4-wire connection

Ways to connect an RTD. Two wires add the full lead resistance to the reading, three wires cancel it if the leads are equal, four wires remove it. See the RTD lead-wire error calculator.

Self-heating

The temperature rise of a sensor caused by its own measuring current. It makes RTDs and thermistors read high; small currents keep it negligible.

Thermocouple

Two dissimilar metals joined at the measuring point; they produce a voltage that depends on the temperature difference to the reference junction. See the thermocouple calculator and the thermocouple types.

Cold junction compensation

Correcting a thermocouple reading for the temperature of the reference (cold) junction, usually the instrument terminals. The correct method adds voltages, not temperatures.

Seebeck coefficient

The sensitivity of a thermocouple, in µV/°C: the slope of its voltage-temperature curve at a given temperature.

Extension and compensating cable

Cable that continues a thermocouple to the instrument. Extension cable uses the thermocouple alloys; compensating cable uses cheaper alloys that match over a limited temperature range.

ITS-90

The International Temperature Scale of 1990. NIST publishes thermocouple reference functions on this scale, adopted in IEC 60584-1.

NTC thermistor

A resistor whose resistance falls steeply with rising temperature. See the NTC thermistor calculator.

Beta value (β, B)

The constant of the NTC Beta model, in kelvin, stated for a pair of temperatures such as B25/85. It describes the curve well near those temperatures only.

Steinhart–Hart equation

1/T = A + B·ln R + C·(ln R)³: an NTC model fitted exactly to three calibration points, accurate over a wide range.

Pressure and transmitters

Gauge, absolute and differential pressure

Pressure relative to the local atmosphere, to vacuum, or between two process points. Units such as bar or psi do not say which; suffixes like barg and bara do. See the pressure unit converter.

URL (upper range limit)

The highest range a pressure transmitter’s sensor can be set to. Temperature effect and stability are usually specified as a percentage of the URL.

Turndown

The ratio of URL to calibrated span. A high turndown makes the URL-based errors large compared with the span.

Reference accuracy

The error of a transmitter at constant laboratory conditions, usually a percentage of span. In service, temperature effect and drift add to it.

Total probable error (TPE)

The combined error of reference accuracy, temperature effect and long-term stability, taken as the root-sum-square. See the pressure transmitter accuracy calculator.

Load cells

Rated output (mV/V)

The signal of a load cell per volt of excitation at full rated load. A 2 mV/V cell at 10 V gives 20 mV at capacity. See the load cell output calculator.

Excitation

The supply voltage across a load cell’s bridge. The output is proportional to it, so six-wire connections sense it at the cell.

Junction (summing) box

The box that connects several load cells in parallel and averages their outputs into one signal.

Dead load and live load

The weight of the platform or vessel (dead load) and of the product being weighed (live load). Both use up capacity; only the live load is weighed.

Division (e)

The smallest weight step a scale displays. Indicators need a minimum signal per division, typically 0.5 to 1 µV.

Threads

G (BSPP) and R (BSPT)

British pipe threads with a 55° flank: G is parallel and seals on a gasket or O-ring (ISO 228-1), R is tapered 1:16 and seals on the thread (ISO 7-1). See the thread identifier and thread dimensions.

NPT

American taper pipe thread with a 60° flank (ASME B1.20.1), sealing on the thread with sealant. Not interchangeable with R threads.

PG

Steel conduit threads to DIN 40430 with an 80° flank, used for older cable glands; largely replaced by metric M threads.

Electronics, current and fieldbus

Modbus register

The 16-bit unit of data in Modbus. Holding registers (4x) can be read and written, input registers (3x) only read. A 32-bit value takes two registers, a 64-bit value four. See the Modbus register decoder.

Byte order (endianness)

The order in which the bytes and registers of a multi-register value arrive. ABCD is big-endian, CDAB swaps the two registers, BADC swaps the bytes in each register, DCBA reverses everything. The protocol does not fix it; the device manual does.

Full scale (FS)

The value an accuracy stated in % FS refers to, usually the span of the measuring range. An error in % FS is the same number of units everywhere in the range. See the sensor accuracy spec converter.

% of reading

An error that scales with the measured value: 0.1 % of reading is 0.01 bar at 10 bar and 0.001 bar at 1 bar. Datasheets often combine it with a % FS term.

ppm

Parts per million: 1 ppm is 0.0001 %. Used for small errors and temperature coefficients, such as 25 ppm/K for a precision resistor.

LSB

Least significant bit: the smallest step of an analogue-to-digital converter, its input range divided by 2^N. See the ADC resolution calculator.

Nyquist frequency and aliasing

Half the sample rate. Signal content above it is not lost but folds back into the measured band as a false low-frequency component, unless a filter removes it before sampling. See the anti-aliasing filter calculator.

Ratiometric measurement

A measurement in which the converter’s reference is taken from the sensor’s excitation, as with bridges and thermistor dividers. A change in the supply then changes signal and reference alike and cancels out.

Instrumentation amplifier

A differential amplifier with high input impedance and common-mode rejection, used for bridges and small sensor signals. The gain is usually set by one resistor, G = 1 + K / RG. See the instrumentation amplifier gain calculator.

E series (E24, E96)

The preferred resistor values of IEC 60063: 24 values per decade for 5 % parts, 96 for 1 % parts, spaced evenly on a logarithmic scale.

Current shunt

A low-value resistor in the current path whose voltage drop measures the current, rated for example 100 A / 75 mV. See the current shunt calculator.

CT burden

The load on the secondary of a current transformer, in volt-amperes at rated secondary current: the cable plus the connected meters and relays. See the current transformer burden calculator.

K-factor

The number of pulses a flow meter gives per unit volume, for example 100 pulses per litre. The pulse frequency is the K-factor times the flow rate. See the pulse output calculator.

Quadrature encoder

An incremental encoder with two channels, A and B, a quarter period apart. Counting the edges of both channels gives up to four counts per pulse and the direction of motion.

Dissipation constant

The power that raises a thermistor’s temperature by one kelvin, in mW/K for a stated mounting. Self-heating is the power in the sensor divided by it. See the NTC voltage divider calculator.

Duty cycle

The share of time a battery-powered device is awake. The average current, and with it the battery life, follows from the current and time of each state. See the battery life calculator.

Shared 0 V (common return)

A conductor that carries both the supply return and the signal reference, as in three-wire sensors with a voltage output. The supply current through its resistance shifts the signal. See the sensor supply voltage drop calculator.

↑ ↓ choose · Enter open · Esc close