4–20 mA to 0–250 bar: scaling table

A transmitter calibrated 0–250 bar: 4 mA = 0 bar, 20 mA = 250 bar. Linear output.

At a glance

Span
250 bar
Change per 1 mA
15.625 bar
Change per 1 %
2.5 bar
Value at 12 mA
125 bar

Scaling table

Current (mA)Output (%)Value (bar)
4.000 %0
6.0012.5 %31.25
8.0025 %62.5
10.0037.5 %93.75
12.0050 %125
14.0062.5 %156.25
16.0075 %187.5
18.0087.5 %218.75
20.00100 %250

Open this range in the 4–20 mA converter

NAMUR NE 43 limits in bar

Current (mA)Value (bar)Meaning
3.6-6.25Failure signal, downscale (≤ 3.6 mA)
3.8-3.125Lower measuring limit (3.8 mA)
20.5257.813Upper measuring limit (20.5 mA)
21.0265.625Failure signal, upscale (≥ 21 mA)

Formula

PV = 0 + (I − 4) / 16 × 250 bar

Example: a reading of 13.6 mA corresponds to 150 bar. Going the other way, 187.5 bar corresponds to 16 mA.