Thermocouple colour code decoder

Identify thermocouple type, polarity (+ / −) and alloys from wire colours across IEC 60584-3, ANSI MC96.1, DIN 43710, JIS C 1610 and BS 1843.

In IEC 60584-3, negative is always white (Type K is green + / white −); in ANSI MC96.1, negative is always red (Type K is yellow + / red −). Legacy DIN 43710 and JIS C 1610 use red for positive (+).

Wire and jacket colours

Presets

Result

Top match
Type KANSI MC96.1 / ASTM E230
Positive (+)
yellowNi-Cr (Chromel)
Negative (−)
redNi-Al (Alumel)
Sheath
yellow-270 … 1372 °C · negative leg (Ni-Al) weakly magnetic

Schematic

Type K · ANSI MC96.1 / ASTM E230-270 … 1372 °Cyellow+ yellowNi-Cr (Chromel)− redNi-Al (Alumel)Negative (−) is always red
Drawn from the inputs above; not to scale.

Matching colour codes

1 matching standard found.

TypeStandardPositive (+)Negative (−)SheathConductors (+ / −)
Type KANSI MC96.1 / ASTM E230yellowredyellowNi-Cr (Chromel) / Ni-Al (Alumel)

Click any row to inspect its polarity and cable diagram above.

Formulas and standards

IEC 60584-3 is the international standard: the negative conductor is always white, and the positive conductor and outer sheath share the type colour. ANSI MC96.1 / ASTM E230 (North America) uses red for every negative conductor.

Legacy national standards reverse that convention: both DIN 43710 (Germany) and JIS C 1610 (Japan) use red for the positive (+) conductor, while BS 1843 (UK) uses blue for the negative (−) conductor.

Because Red + Blue can mean ANSI Type T (Red = −) or DIN 43710 Type J (Red = +), never guess polarity by colour alone in mixed-vintage plants. Check the sheath colour, test with a magnet (Type J + Iron is strongly magnetic; Type K − Alumel is weakly magnetic) or warm the tip and verify positive mV rise.

Need certified IEC or ANSI thermocouple cable or probes?

Contact us

How thermocouple colour codes differ by standard

Every thermocouple cable uses two dissimilar alloys, so reversing the wires at a junction box introduces a double-sized temperature error. Worse, the five major colour standards disagree on which colour means positive and which means negative:

Standard Region Polarity rule Type K (+ / − / sheath)
IEC 60584-3 International / EU Negative (−) is always white Green / White / Green
ANSI / ASTM E230 North America Negative (−) is always red Yellow / Red / Yellow
DIN 43710 (legacy) Germany / Europe Positive (+) is always red Red / Green / Green
JIS C 1610 (legacy) Japan Positive (+) red, negative (−) white Red / White / Blue
BS 1843 (legacy) United Kingdom Negative (−) is always blue Brown / Blue / Red

Because the tool checks Wire 1 and Wire 2 in either order, you can select the two colours you see in the terminal box without guessing polarity first.

The most dangerous polarity traps

Red + Blue: Under ANSI / ASTM E230 this is Type T with Red as negative (−) and Blue as positive (+). Under legacy DIN 43710 this is Type J with Red as positive (+) and Blue as negative (−). Both standards even use a blue outer sheath.

Red + White: Under ANSI / ASTM E230 this is Type J with Red as negative (−). Under DIN 43710 (Type R/S) and every JIS C 1610 thermocouple cable, Red is positive (+) and White is negative (−).

Green + Red vs Green + White: Green + White is always IEC 60584-3 Type K (Green = +). Red + Green is legacy DIN 43710 Type K (Red = +).

Field tests when colours are faded or ambiguous

When high heat has browned the insulation or a plant mixes US, European and Japanese equipment, verify the cable physically before terminating:

  1. Magnet test: On Type J, the positive Iron leg is strongly magnetic. On Type K, the negative Alumel (Ni-Al) leg is weakly magnetic while the positive Chromel leg is non-magnetic. Types T, E, N, R, S and B are non-magnetic on both legs.
  2. Warm-tip multimeter test: Connect a millivoltmeter to the free ends and warm the measuring junction with your fingers or a heat gun. The wire connected to the meter’s positive (+) lead that produces a rising positive mV reading is the true positive leg. Convert the reading to temperature with the thermocouple calculator or review full EMF curves on thermocouple types.

Frequently asked questions

Is red positive or negative on a thermocouple?

It depends on the standard. In North America (ANSI / ASTM E230), red is always negative (−). In legacy German DIN 43710 and Japanese JIS C 1610 cables, red is positive (+). In modern IEC 60584-3 cables, red is not used for any standard thermocouple conductor.

What thermocouple has a yellow and red wire?

Yellow (+) and Red (−) inside a yellow jacket is Type K under ANSI / ASTM E230 (Chromel positive, Alumel negative).

What thermocouple has a green and white wire?

Green (+) and White (−) inside a green jacket is Type K under IEC 60584-3.

Can I join IEC and ANSI Type K cables together?

Yes, provided you match the alloys and polarity, not the colours: connect IEC Green (+) to ANSI Yellow (+), and IEC White (−) to ANSI Red (−), using a Type K terminal block or connector.