Type T thermocouple

Cu / Cu-Ni · -270 … 400 °C · IEC 60584-1

At a glance

Conductors (+ / −)
Cu / Cu-Ni
Range of the reference function
-270 … 400 °C
Sensitivity at 100 °C
46.78 µV/°C
Class 1 tolerance
±0.5 °C or ±0.004 × |t|, whichever is larger, -40 to 350 °C
Class 2 tolerance
±1 °C or ±0.0075 × |t|, whichever is larger, -40 to 350 °C
Class 3 tolerance
±1 °C or ±0.015 × |t|, whichever is larger, -200 to 40 °C
Extension and compensating cable
TXIEC 60584-3: X = extension cable of the same alloys, C = compensating cable of other alloys, matched over a limited temperature range

Wire colours

PositiveNegativeSheath / Jacket
IEC 60584-3 (international)brownwhitebrown
ASTM E230 / ANSI (USA), extension wireblueredblue

Colours identify the type, not the quality of the cable. Older national codes (e.g. BS 1843, DIN 43714, JIS) used other colours; check before reusing existing cable.

EMF and tolerance at common temperatures (0 °C reference)

Temperature (°C)EMF (mV)Sensitivity (µV/°C)Class 1 (±°C)Class 2 (±°C)Class 3 (±°C)
-200-5.60315.74——±3.00
-100-3.37928.39——±1.50
00.00038.75±0.50±1.00±1.00
502.03642.82±0.50±1.00—
1004.27946.78±0.50±1.00—
2009.28853.15±0.80±1.50—
30014.86258.09±1.20±2.25—
40020.87261.80———

—: the class is not defined at this temperature. Tolerance of type T at every 100 °C

Full type T EMF tableThermocouple calculator

Typical use and limits

Copper against constantan: the most accurate base-metal type near ambient and below zero, used in food, pharmaceutical, laboratory and cryogenic work. The copper leg oxidises above about 370 °C, which sets the practical upper limit. Copper conducts heat well, so watch for stem conduction errors in short immersion lengths.