Type K thermocouple
Ni-Cr / Ni-Al · -270 … 1372 °C · IEC 60584-1
At a glance
- Conductors (+ / −)
- Ni-Cr / Ni-Al
- Range of the reference function
- -270 … 1372 °C
- Sensitivity at 400 °C
- 42.24 µV/°C
- Class 1 tolerance
- ±1.5 °C or ±0.004 × |t|, whichever is larger, -40 to 1000 °C
- Class 2 tolerance
- ±2.5 °C or ±0.0075 × |t|, whichever is larger, -40 to 1200 °C
- Class 3 tolerance
- ±2.5 °C or ±0.015 × |t|, whichever is larger, -200 to 40 °C
- Extension and compensating cable
- KX · KCA · KCBIEC 60584-3: X = extension cable of the same alloys, C = compensating cable of other alloys, matched over a limited temperature range
Wire colours
| Positive | Negative | Sheath / Jacket | |
|---|---|---|---|
| IEC 60584-3 (international) | green | white | green |
| ASTM E230 / ANSI (USA), extension wire | yellow | red | yellow |
Colours identify the type, not the quality of the cable. Older national codes (e.g. BS 1843, DIN 43714, JIS) used other colours; check before reusing existing cable.
EMF and tolerance at common temperatures (0 °C reference)
| Temperature (°C) | EMF (mV) | Sensitivity (µV/°C) | Class 1 (±°C) | Class 2 (±°C) | Class 3 (±°C) |
|---|---|---|---|---|---|
| -200 | -5.891 | 15.26 | — | — | ±3.00 |
| 0 | 0.000 | 39.45 | ±1.50 | ±2.50 | ±2.50 |
| 100 | 4.096 | 41.37 | ±1.50 | ±2.50 | — |
| 200 | 8.138 | 39.97 | ±1.50 | ±2.50 | — |
| 400 | 16.397 | 42.24 | ±1.60 | ±3.00 | — |
| 600 | 24.905 | 42.51 | ±2.40 | ±4.50 | — |
| 800 | 33.275 | 41.00 | ±3.20 | ±6.00 | — |
| 1000 | 41.276 | 38.98 | ±4.00 | ±7.50 | — |
| 1200 | 48.838 | 36.49 | — | ±9.00 | — |
—: the class is not defined at this temperature. Tolerance of type K at every 100 °C
Typical use and limits
The general-purpose type: wide range, inexpensive and accepted by almost every instrument. Two drift mechanisms limit long-term accuracy: short-range ordering in the positive leg between about 250 and 600 °C, and preferential oxidation of chromium ("green rot") in low-oxygen atmospheres at high temperature. For long service above about 800 °C, type N is often the better choice.