1. 回路概要と動作原理
RS-485 (TIA/EIA-485-A) is the undisputed industrial fieldbus workhorse for Modbus RTU sensors, smart meters, VFDs, and building automation — spanning up to 1,200 meters and 256 nodes over a single twisted pair with extreme noise immunity.
Rock-solid RS-485 hardware relies on four golden rules: true daisy-chain topology (no long stubs), exactly TWO 120 Ω end-of-line termination resistors (NEVER on middle nodes!), fail-safe idle biasing holding V_AB > +200 mV when all drivers release the bus, and asymmetric surge TVS protection (SM712, −7 V to +12 V).
Balanced Differential Polarity Flip: Sending Logic 1 (MARK) drives A > B (current flows A → 120 Ω → B); Logic 0 (SPACE) flips polarity so B > A (current REVERSES B → 120 Ω → A!). Any EMI coupled equally onto both twisted wires cancels out cleanly at the differential receiver.
Why Idle Fail-Safe Biasing Eliminates Random Modbus Errors: Between half-duplex packets, every driver tri-states. Without pull-up/pull-down bias resistors, the two 120 Ω terminators pull V_AB straight to 0.0 mV — dead center in the ±200 mV undefined zone! Placing Rb (560 Ω on 5 V, 390 Ω on 3.3 V) at ONE bus location holds V_AB > +200 mV so every receiver sees a rock-solid idle MARK.

2. Step-by-step: Designing & commissioning an industrial RS-485 / Modbus bus
1Wire strictly daisy-chain with 120 Ω shielded twisted pair + 3rd GND ref
Run A/B as a true daisy-chain (keep drop stubs < 1 m) and ALWAYS include a 3rd common reference conductor (or isolated transceivers) so common-mode stays inside the −7 V to +12 V RS-485 spec!
2Install 120 Ω termination ONLY at the two physical ends of the cable
Measure resistance between A and B with power off: two 120 Ω end terminators read ~60 Ω. If you measure 40 Ω or 30 Ω, extra terminators are accidentally switched ON in the middle!
3Enable fail-safe idle bias at ONE node (or use true fail-safe transceivers)
Install 560 Ω pull-up on A and 560 Ω pull-down on B at the master (5 V), OR use modern true fail-safe transceivers (THVD1450 / MAX3082) whose receiver threshold is shifted to −50…−200 mV.
4Protect A/B with SM712 asymmetric TVS + 10 Ω pulse-proof series resistors
Never use a symmetric 5 V TVS on RS-485 — it clips valid −7 V to +12 V common-mode swings! Use SM712 (−7 V / +12 V) paired with two 10 Ω surge resistors.
3. 現場トラブルシューティングとテスタ確認
| 症状 | 原因 | テスタ測定ポイント | 対策 |
|---|---|---|---|
| Modbus master gets zero responses on a freshly wired bus | A and B polarity swapped (different vendors disagree on A/B vs D+/D− naming!) | Measure idle V_A − V_B: A (D+) MUST be positive relative to B (D−) | Swap A and B wires at the non-responding sensor (safe — RS-485 is short/swap tolerant) |
| Random CRC errors or extra 0x00 bytes between valid Modbus packets | Missing fail-safe idle bias (V_AB = 0 mV during bus turnaround) or missing 120 Ω termination | Measure V_AB when bus is idle (must be > +200 mV) and power-off R_AB (~60 Ω) | Add 560 Ω fail-safe bias at master and verify exactly two 120 Ω end terminators |
4. よくある技術質問(FAQ)
Why does RS-485 STILL need a 3rd signal ground wire if it is differential?
Transceivers only survive −7 V to +12 V of common-mode voltage relative to their local GND pin. Between distant buildings or cabinets, floating grounds can easily drift 15–30 V apart, saturating or frying the transceiver unless tied via a 3rd reference wire (or isolated transceivers like ADM2587E).
What should a multimeter read across A and B when power is OFF?
With proper 120 Ω termination resistors at BOTH physical ends, A-to-B measures ~60 Ω (120 Ω || 120 Ω). ~120 Ω means one end is missing; >1 kΩ means no terminators; <45 Ω means too many middle nodes have termination enabled!
Why is the SM712 TVS diode famous for RS-485 protection?
SM712 is specifically engineered with asymmetric breakdown voltages (−7 V and +12 V) matching the exact TIA/EIA-485-A common-mode window — protecting transceivers from 30 kV ESD and 400 W surges without clipping valid bus signals.
Do I need 120 Ω terminators on a short 5-meter 9600 bps Modbus bus?
At 9600 bps over <20 m, signal reflections settle well before bit sampling, so termination is often optional — saving power and easing fail-safe bias. Above ~50–100 m or ≥115.2 kbps, dual 120 Ω termination becomes essential.
Can I put fail-safe bias resistors on EVERY RS-485 sensor node?
NO! Paralleling 560 Ω bias resistors across 16 nodes drops the bus impedance to ~35 Ω, overloading transceivers and killing signal amplitude! Place fail-safe bias resistors at ONE location only (typically the PLC/master end).
Why are RS-485 A and B labels often backwards between manufacturers?
The original TIA-485 standard defined A as negative during idle MARK, whereas IC makers (TI/Maxim) historically labeled the non-inverting positive pin as A (D+). Always trust D+/D− polarity: idle D+ > D− by at least +200 mV!