1. 回路概要と動作原理
When an active analog sensor (0–10 V or 3-wire 4–20 mA) draws 20–120 mA of operating power — common for laser distance, ultrasonic level, and Coriolis flow meters — how the 0 V return wire is wired makes or breaks measurement accuracy.
In a 3-wire hookup, supply return current and the 0–10 V signal share one 0 V conductor. Ohm’s law (ΔV = I_sup × R_0V) silently elevates the sensor’s local 0 V above the PLC’s 0 V, injecting a direct positive zero-shift error into every reading. Upgrading to 4-wire separate signal return (or galvanic isolation) eliminates this shift completely.
3-Wire Ground-Shift Math: A 50 mA sensor over 60 m of 0.34 mm² cable (3.04 Ω) plus 0.5 Ω terminal resistance develops ΔV = 0.05 A × 3.54 Ω = +177 mV — a massive +1.77% full-scale error on a 0–10 V channel, and worse if the sensor’s power draw pulses with an LCD backlight or ultrasonic ping!
4-Wire Kelvin Separation & Single-Point Shielding: Giving the signal its own dedicated return wire (Sig−) into a differential PLC AI means only microamps (~50 µA into 100 kΩ) flow on the reference wire, slashing voltage drop by 1000×. Always ground cable shields at ONE end only (the PLC cabinet) to prevent destructive plant earth ground loops.

2. Step-by-step: Eliminating 0–10 V ground shift and ground loops in the field
1Check cable length × sensor supply current before using 3-wire 0–10 V
Compute ΔV = I_sup × R_0V. If ΔV exceeds 0.1%–0.25% of full scale (10–25 mV on 0–10 V), do NOT share the 0 V return — use 4-wire wiring or switch the sensor to 4–20 mA current mode.
2Run a dedicated 4th wire (Sig−) straight from sensor 0 V to PLC AI−
Even on a 3-terminal sensor, running a separate 4th sense wire from the sensor’s 0 V terminal directly to the PLC differential AI− terminal (star-point at the sensor!) eliminates return-wire drop.
3Eliminate dual-point earth ground loops
Verify the field sensor’s 0 V is NOT bonded to local pipe/frame earth if the PLC cabinet 0 V is already earthed. Where grounded probes are unavoidable, insert a 1:1 galvanic analog isolator.
4Verify with a differential multimeter check at 0% (zero point)
At zero physical input, measure voltage right at the sensor terminals vs at the PLC AI terminals. Any difference > 5 mV reveals shared-return drop or earth-loop current.
3. 現場トラブルシューティングとテスタ確認
| 症状 | 原因 | テスタ測定ポイント | 対策 |
|---|---|---|---|
| PLC reads +0.15 V to +0.40 V even when sensor is at true zero | 3-wire shared 0 V return drop from sensor supply current (or oxidized 0 V terminal) | Measure DC millivolts between sensor 0 V terminal and PLC 0 V terminal | Add a 4th dedicated signal-return wire to PLC AI−, thicken 0 V wire, or switch to 4–20 mA |
| Wild ±0.5–1.5 V offset shifts whenever nearby motors/VFDs start | Dual-point earth ground loop injecting plant earth voltage difference | Disconnect field-end shield/0 V earth bond and watch offset vanish | Maintain single-point earthing at cabinet or install a 3-way galvanic signal isolator |
4. よくある技術質問(FAQ)
What is the main difference between 2-wire, 3-wire, and 4-wire analog transmitters?
2-wire (always 4–20 mA) shares 2 wires for power and signal (draws <3.5 mA internally). 3-wire shares one common 0 V return between power and signal. 4-wire uses two completely separate wires for power and two for the analog signal (often galvanically isolated).
Why does a 3-wire 4–20 mA transmitter avoid ground-shift error unlike 3-wire 0–10 V?
Because a current-output stage actively regulates loop current into the PLC’s 250 Ω input regardless of moderate 0 V wire voltage shift, whereas a voltage output references its signal directly against the shifted local 0 V node!
Can I turn a 3-wire 0–10 V sensor into a 4-wire connection in the field?
Yes! Run a 4-core cable and tie the dedicated Sig− wire right at the sensor’s 0 V screw terminal, routing it straight to the PLC differential AI− input. That keeps power return current off the measurement reference wire.
Where should the cable shield be grounded for an analog transmitter?
Ground the shield at ONE end only — almost always the PLC/control cabinet PE bar — and insulate the drain wire cleanly at the field sensor end to prevent ground-loop currents flowing down the shield.
How long can a 3-wire 0–10 V cable run before accuracy suffers?
As a rule of thumb, keep 3-wire 0–10 V runs under 15–30 m (especially if sensor supply draw exceeds 30 mA). Beyond 30 m, switch to 4-wire Kelvin return or 4–20 mA.
What is a galvanic 3-way analog isolator?
A 3-way isolator electrically separates Power Supply, Input Signal, and Output Signal with transformers/optocouplers (typically 1.5–2.5 kVrms), breaking every possible ground loop in a single DIN-rail module.