RS-485: Terminación 120 Ω, Polarización Fail-Safe y TVS

Balanced Differential Half-Duplex · 3.3 V / 5.0 V Transceiver

Un bus RS-485 robusto requiere dos terminadores de 120 Ω en los extremos (60 Ω), polarización fail-safe en un punto (V_AB > +200 mV en reposo), 3er hilo de referencia y TVS SM712.

TX MARK (Logic 1): V_AB = +2100 mV · Bus Current 35.4 mA (A → B)

Well above the +1500 mV TIA/EIA-485-A loaded driver spec across 59.4 Ω effective bus load (16 nodes + 2 × 120 Ω).

Flujo normalAlerta / LimitaciónFallo / SobrecorrienteVelocidad ∝ |I|
RS-485 MasterTX / RX · +5.0 V+2100 mV35.4 mALine A (D+) — Twisted PairLine B (D−) · 16 Nodes120 Ω+Vcc · Rb=560 ΩGND · Rb=560 ΩTVS SM712−7V / +12V120 ΩRemote Node1/8 UL (96 kΩ)+2100 mVModbus RTU3rd Signal Reference Ground (−7…+12 V CM Limit)

Differential Voltage (V_A − V_B)

+2100 mV

Differential Terminator Current

35.4 mA

Effective Bus Load (Rt/2 || Nodes)

59.4 Ω

UART Decoded Logic

LOGIC 1 (MARK)

Dual-End Termination2 × 120 Ω (Eq 60 Ω)
Fail-Safe Idle Bias (>200 mV)ACTIVE (560 Ω OK)
Asymmetric RS-485 Surge TVSSM712 (−7 V to +12 V)
Unit-Load Bus Capacity16 / 256 (1/8 UL OK)
Ω

Standard twisted-pair characteristic impedance Z0 is 120 Ω (two ends = 60 Ω).

Ω

560 Ω on 5 V (or 390 Ω on 3.3 V) holds idle V_AB > +200 mV!

V

5.0 V (MAX485 / ADM485) or 3.3 V (MAX3485 / THVD1450).

nodes

Standard 1 UL allows 32 nodes; 1/8 UL transceivers allow up to 256 nodes!

Preajustes:

Fórmulas paso a paso en vivo

1. Effective differential bus resistance

R_bus = (R_t / 2) || (96 kΩ / N) = (120 / 2) || (96k / 16)

⇒ 59.4 Ω

2. Idle fail-safe voltage across A–B

V_AB(idle) = V_cc · R_bus / (2·R_b + R_bus) = 5.0 × 59.4 / (2×560 + 59.4)

⇒ +252 mV (Need ≥ +200 mV)

3. Active differential terminator current

I_bus = V_AB / R_bus = 2100 mV / 59.4 Ω

⇒ 35.4 mA (A → B)

Lista de materiales dinámica (BOM)

Ref.ComponenteEspecificación calculadaEstado
U1True Fail-Safe 1/8-UL RS-485 TransceiverTHVD1450 / MAX3485E / ADM2587E (isolated)OK
RtEnd-of-Line Termination Resistors (2×)2 × 120 Ω ±1%, 0.5 W (NEVER on middle nodes!)OK
TVS1Asymmetric RS-485 TVS Protection ArraySM712 (−7 V / +12 V) + 2 × 10 Ω pulse-proof series ROK

1. Descripción general y principio de funcionamiento

RS-485 (TIA/EIA-485-A) is the undisputed industrial fieldbus workhorse for Modbus RTU sensors, smart meters, VFDs, and building automation — spanning up to 1,200 meters and 256 nodes over a single twisted pair with extreme noise immunity.

Rock-solid RS-485 hardware relies on four golden rules: true daisy-chain topology (no long stubs), exactly TWO 120 Ω end-of-line termination resistors (NEVER on middle nodes!), fail-safe idle biasing holding V_AB > +200 mV when all drivers release the bus, and asymmetric surge TVS protection (SM712, −7 V to +12 V).

Balanced Differential Polarity Flip: Sending Logic 1 (MARK) drives A > B (current flows A → 120 Ω → B); Logic 0 (SPACE) flips polarity so B > A (current REVERSES B → 120 Ω → A!). Any EMI coupled equally onto both twisted wires cancels out cleanly at the differential receiver.

Why Idle Fail-Safe Biasing Eliminates Random Modbus Errors: Between half-duplex packets, every driver tri-states. Without pull-up/pull-down bias resistors, the two 120 Ω terminators pull V_AB straight to 0.0 mV — dead center in the ±200 mV undefined zone! Placing Rb (560 Ω on 5 V, 390 Ω on 3.3 V) at ONE bus location holds V_AB > +200 mV so every receiver sees a rock-solid idle MARK.

RS-485: Terminación 120 Ω, Polarización Fail-Safe y TVS — SensorCatalog
RS-485 Terminación y BiasPNG 1200×630

2. Step-by-step: Designing & commissioning an industrial RS-485 / Modbus bus

  1. 1Wire strictly daisy-chain with 120 Ω shielded twisted pair + 3rd GND ref

    Run A/B as a true daisy-chain (keep drop stubs < 1 m) and ALWAYS include a 3rd common reference conductor (or isolated transceivers) so common-mode stays inside the −7 V to +12 V RS-485 spec!

  2. 2Install 120 Ω termination ONLY at the two physical ends of the cable

    Measure resistance between A and B with power off: two 120 Ω end terminators read ~60 Ω. If you measure 40 Ω or 30 Ω, extra terminators are accidentally switched ON in the middle!

  3. 3Enable fail-safe idle bias at ONE node (or use true fail-safe transceivers)

    Install 560 Ω pull-up on A and 560 Ω pull-down on B at the master (5 V), OR use modern true fail-safe transceivers (THVD1450 / MAX3082) whose receiver threshold is shifted to −50…−200 mV.

  4. 4Protect A/B with SM712 asymmetric TVS + 10 Ω pulse-proof series resistors

    Never use a symmetric 5 V TVS on RS-485 — it clips valid −7 V to +12 V common-mode swings! Use SM712 (−7 V / +12 V) paired with two 10 Ω surge resistors.

3. Diagnóstico en campo y pruebas con multímetro

SíntomaCausa raízPrueba con multímetroSolución
Modbus master gets zero responses on a freshly wired busA and B polarity swapped (different vendors disagree on A/B vs D+/D− naming!)Measure idle V_A − V_B: A (D+) MUST be positive relative to B (D−)Swap A and B wires at the non-responding sensor (safe — RS-485 is short/swap tolerant)
Random CRC errors or extra 0x00 bytes between valid Modbus packetsMissing fail-safe idle bias (V_AB = 0 mV during bus turnaround) or missing 120 Ω terminationMeasure V_AB when bus is idle (must be > +200 mV) and power-off R_AB (~60 Ω)Add 560 Ω fail-safe bias at master and verify exactly two 120 Ω end terminators

4. Preguntas frecuentes (FAQ)

Why does RS-485 STILL need a 3rd signal ground wire if it is differential?

Transceivers only survive −7 V to +12 V of common-mode voltage relative to their local GND pin. Between distant buildings or cabinets, floating grounds can easily drift 15–30 V apart, saturating or frying the transceiver unless tied via a 3rd reference wire (or isolated transceivers like ADM2587E).

What should a multimeter read across A and B when power is OFF?

With proper 120 Ω termination resistors at BOTH physical ends, A-to-B measures ~60 Ω (120 Ω || 120 Ω). ~120 Ω means one end is missing; >1 kΩ means no terminators; <45 Ω means too many middle nodes have termination enabled!

Why is the SM712 TVS diode famous for RS-485 protection?

SM712 is specifically engineered with asymmetric breakdown voltages (−7 V and +12 V) matching the exact TIA/EIA-485-A common-mode window — protecting transceivers from 30 kV ESD and 400 W surges without clipping valid bus signals.

Do I need 120 Ω terminators on a short 5-meter 9600 bps Modbus bus?

At 9600 bps over <20 m, signal reflections settle well before bit sampling, so termination is often optional — saving power and easing fail-safe bias. Above ~50–100 m or ≥115.2 kbps, dual 120 Ω termination becomes essential.

Can I put fail-safe bias resistors on EVERY RS-485 sensor node?

NO! Paralleling 560 Ω bias resistors across 16 nodes drops the bus impedance to ~35 Ω, overloading transceivers and killing signal amplitude! Place fail-safe bias resistors at ONE location only (typically the PLC/master end).

Why are RS-485 A and B labels often backwards between manufacturers?

The original TIA-485 standard defined A as negative during idle MARK, whereas IC makers (TI/Maxim) historically labeled the non-inverting positive pin as A (D+). Always trust D+/D− polarity: idle D+ > D− by at least +200 mV!