SensorCatalog
IEC 60947-5-2IEC 61131-23-wire (BN +Vcc, BU 0V, BK Out)

PNP(ソース型)3線式センサ出力回路シミュレータ

High-side Sourcing (+Vcc ON) · 10–30 V DC (24 V nom)

3線式PNP(ソース)センサは内蔵ハイサイドトランジスタで+24 V(茶)を黒線へ出力し、0 V基準のシンク型PLC入力へ電流を吐き出します(IEC 61131-2:15 V以上・2 mA以上)。

PLC DI = HIGH (22.49 V · 7.50 mA) — IEC 61131-2 Compliant

PNP transistor is saturated. Sourcing current flows from +24.0 V through Brown → sensor → Black → PLC DI → 0 V.

正常電流フロー警告・クランプ故障・過電流速度 ∝ 電流 |I|
DC PSU+24.0 V15.5 mA0 V (COM)BN (+Vcc)3-Wire PNP Sensor (IEC 60947-5-2)TARGETSensingIC / Osc8.0 mAPNPQ1PWROUTBK (Source Out)7.50 mA22.49 VWIRE BREAKSHORT 0V!PLC Sinking DIIEC 61131-2 (COM=0V)HIGHR_L3.00 kΩ22.49 VBU (0 V Return)2-way cable resistance R_wire = 1.52 Ω

PLC Input Voltage (VDI)

22.49 V

Output Sourcing Current (IL)

7.50 mA

Total Brown-Wire Current

15.50 mA

Load Power / Sensor Heat

169 / 203 mW

Power LED (Green)ON · 24 V OK
Sensor Output LED (Yellow)ON (Active)
PNP Transistor StateSATURATED (ON)
PLC Sinking DI ChannelLOGIC 1 (HIGH)
V

Standard industrial DC rail is 24 V (10–30 V DC).

Ω

PLC Type 1/3 sinking DI is typically 2.2–4.7 kΩ; relay coil 120–1200 Ω.

V

Internal PNP BJT + protection diode drop (typically 1.0–2.5 V).

mA

Standard M12 proximity switches are rated 100–200 mA.

m

0.34 mm² sensor cordset (approx. 50.7 mΩ/m per conductor).

プリセット:

リアルタイム計算式

1. Loop cable resistance (0.34 mm² Cu)

R_wire = 2 · L · ρ / A = 2 × 15 m × 0.01724 / 0.34

⇒ 1.52 Ω

2. Sourcing output current (ON state)

I_L = (V_CC − V_sat) / (R_L + R_wire) = (24.0 − 1.5) / (3000 + 1.52)

⇒ 7.50 mA

3. PLC terminal voltage

V_DI = I_L · R_L = 0.00750 A × 3000 Ω

⇒ 22.49 V (HIGH)

動的部品選定・BOM

記号部品推奨定格判定
PS124 V DC Industrial PSU24.0 V DC, ≥ 24 mA per channelOK
S13-Wire PNP Sensor (NO/NC)BN=+Vcc, BU=0V, BK=Out (Imax 200 mA, Vsat 1.5 V)OK
PLC1Sinking PLC Digital Input (COM = 0 V)IEC 61131-2 Type 1/3, R_in ≈ 3000 Ω (P = 169 mW)OK

1. 回路概要と動作原理

A 3-wire PNP (sourcing) sensor is the default discrete sensor interface in European and North American factory automation. Its IEC 60947-5-2 color code is Brown (+Vcc, pin 1), Blue (0 V, pin 3), and Black (switched output, pin 4).

Internally, a PNP bipolar transistor or P-channel MOSFET connects the Black wire up to the +24 V rail whenever the target is detected. Because current flows OUT of the sensor into the load (PLC digital input or relay coil) and then to 0 V, the sensor "sources" current while the PLC input "sinks" it.

Standby (OFF): The internal oscillator/comparator holds the PNP base high, keeping the transistor cut off. Only the sensor quiescent supply current (~5–15 mA) flows from Brown to Blue. The PLC input resistor pulls the Black terminal cleanly to 0 V (Logic 0).

Triggered (ON): The PNP stage saturates with a small internal drop Vsat (typically 1.0–2.5 V including reverse-polarity protection diode). Terminal voltage at the PLC reaches Vcc − Vsat − I·Rwire (~22 V on a 24 V rail), well above the IEC 61131-2 Type 1/3 Logic 1 threshold (15 V, ≥ 2 mA).

Fail-safe behavior: If the Black signal wire breaks or gets pinched against a grounded metal frame (0 V), the PLC input drops to 0 V instead of generating a false "target present" signal. Short-circuit protected sensors automatically fold back current so the transistor survives.

PNP(ソース型)3線式センサ出力回路シミュレータ — SensorCatalog
PNP ソース出力回路PNG 1200×630

2. Step-by-step: How to wire and commission a 3-wire PNP sensor

  1. 1Verify PLC input card polarity (Sinking / COM = 0 V)

    Check the PLC DI wiring diagram before powering on. For PNP sensors, the PLC DI common terminal (M / COM / SS) MUST connect to 0 V DC so current sourced from the sensor can return to the power supply.

  2. 2Wire Brown (+24 V), Blue (0 V), and Black (PLC DI)

    Connect Brown (Pin 1) to +24 V DC, Blue (Pin 3) to 0 V DC, and Black (Pin 4) directly to the PLC input terminal (e.g. I0.0). Keep inductive relay loads below the sensor Imax rating (typically 100–200 mA) and add a flyback diode across any relay coil.

  3. 3Verify supply & standby voltage with a multimeter

    Power up and confirm the sensor Green power LED is ON. Measure DC voltage from Black to Blue with no target: it must read < 1 V (typically 0.0–0.2 V).

  4. 4Trigger target and verify IEC 61131-2 Logic 1 margin

    Place a metal/optical target in range. Confirm the sensor Yellow LED and PLC channel LED both light up, and measure Black-to-Blue voltage ≥ 18 V (guaranteed > 15 V IEC 61131-2 threshold).

3. 現場トラブルシューティングとテスタ確認

症状原因テスタ測定ポイント対策
Sensor yellow LED lights, PLC DI LED stays OFFPLC COM wired to +24 V (Sourcing DI mismatch) or broken Black wireMeasure Black-to-Blue at sensor (22 V) vs at PLC terminal (0 V or 22 V)Move PLC COM to 0 V (or add PNP-to-NPN converter/relay); repair cable
Yellow LED blinks rapidly and output voltage collapsesOutput shorted to 0 V or load resistance too low (exceeds Imax)Disconnect Black wire; if yellow LED becomes steady and reads ~22.5 V, fault is downstreamClear short to chassis or drive heavy load via an interposing relay
Voltage at PLC drops below 15 V on long cable runsExcessive cable resistance + low-resistance relay/lamp loadMeasure Vcc at sensor Brown-Blue while ONUpgrade cable cross-section (0.5–0.75 mm²) or raise PSU to 24.5–26 V

4. よくある技術質問(FAQ)

Does a PNP sensor connect to a Sinking or Sourcing PLC input?

A PNP (sourcing) sensor MUST connect to a Sinking PLC input (common terminal tied to 0 V DC). The sensor sources positive current out of its Black wire, and the PLC input sinks that current to 0 V.

Why does a PNP output measure ~22.5 V instead of 24.0 V when ON?

Internal semiconductor junctions — specifically the PNP output transistor Vce(sat) and series reverse-polarity protection diode — drop 1.0 to 2.5 V under load. This is completely normal per IEC 60947-5-2.

Can I connect two PNP NO sensors in parallel for OR logic?

Yes, most modern PNP sensors include reverse-blocking diodes so tying Black wires together performs wired-OR logic. Confirm the datasheet allows parallel connection to avoid reverse leakage back-feeding the inactive sensor.

Why is PNP preferred over NPN in safety-critical machinery?

Because industrial machine frames are bonded to 0 V DC ground. If a PNP Black wire chafes and shorts to the frame, the output collapses to 0 V (fail-safe). On an NPN sensor, a ground short mimics an active trigger and causes an unintended start!

Do I need an external pull-down resistor for a PNP sensor?

No for standard PLC inputs (which already have 2.2–4.7 kΩ internal input impedance to 0 V). Only add a 4.7–10 kΩ pull-down resistor if feeding a very high-impedance CMOS/MCU input (>1 MΩ) to drain microamp OFF-state leakage.

How do I interface a 24 V PNP sensor to a 3.3 V or 5 V microcontroller?

Never wire 24 V directly to an MCU pin. Use an optocoupler (e.g. PC817 with a 2.2–3.3 kΩ series input resistor) for full galvanic isolation, or a precision resistor divider (e.g. 68 kΩ / 10 kΩ) plus a 3.3 V Zener/Schottky clamp.