1. Présentation & principe de fonctionnement
Every 24 V industrial sensor module or PLC expansion board must survive three field realities: reversed power wiring (−24 V), relay/motor inductive surges (+40–60 V), and downstream short circuits. Combining a polymeric PTC fuse, SMBJ28A TVS, and a P-channel MOSFET with a 12 V Zener gate clamp delivers bulletproof protection with millivolt drop.
Why PMOS Beats a Diode: A 1N4007 or Schottky diode wastes 0.5–0.8 V and heats up at high current. A back-wired PMOS (drain to input, source to load) conducts through its 45 mΩ channel during normal polarity (only ~7 mV drop at 150 mA!) yet blocks −24 V completely when reversed.
Mandatory 12 V Zener Gate Clamp: Most PMOS gates rupture above ±20 V! On a 24 V industrial rail (plus 38 V TVS surges), tying Gate directly to GND destroys Q1 immediately. Placing a 12 V Zener between Gate and Source + 100 kΩ to GND locks Vgs safely at −12 V.

2. Step-by-step: Building a bulletproof 24 V sensor power entry stage
1Size PTC I_hold ≥ 1.8× max load to survive 60 °C cabinets
Polymeric PTC fuses derate by ~30% at 60 °C ambient; undersizing causes mysterious random resets.
2Select SMBJ28A TVS (Vrwm = 28 V) after the PTC
Place TVS AFTER the PTC so sustained overvoltage trips the PTC instead of exploding the TVS.
3Orient PMOS Source toward the load and Drain toward input
Verify body diode anode faces Drain so forward power starts conduction and reverse polarity blocks!
4Add 12 V Zener across G–S + 100 kΩ gate resistor
Use a −40 V or −60 V rated PMOS so it survives the ~38–45 V clamping peak of the SMBJ28A.
3. Dépannage terrain & mesures au multimètre
| Symptôme | Cause racine | Contrôle multimètre | Action corrective |
|---|---|---|---|
| PMOS shorts out permanently on first 24 V power-up | Missing 12 V Zener clamp — 24 V exceeded PMOS ±20 V Vgs(max) rating | Measure Gate-to-Source resistance (often <10 Ω after gate punch-through) | Install 12 V Zener (BZT52C12) across G–S and 100 kΩ to GND |
4. Questions fréquentes (FAQ)
Why put the TVS diode after the PTC instead of before it?
If someone applies a continuous 36 V overvoltage, the TVS conducts heavily; placing the PTC upstream lets the PTC trip and protect the TVS from burning up.
5. Calculateurs associés, guides et autres circuits
- Calculateur de chute de tension d’alimentation de capteur
- Calculateur d’autonomie de pile
- Sortie Capteur PNP 3 Fils (Source) — Schéma & Simulateur
- Sortie Capteur NPN 3 Fils (Sink / Collecteur Ouvert)
- Circuit NAMUR 2 Fils Sécurité Intrinsèque (IEC 60947-5-6)
- Sortie Push-Pull (HTL/TTL) & Drain Ouvert — Simulateur
- Isolation Optocoupleur & Relais avec Diode de Roue Libre
- Contact Sec : Anti-Rebond Matériel RC & Courant de Mouillage
- Boucle de Courant 4–20 mA 2 Fils & Récepteur Protégé
- Transmetteur Analogique Actif 3 Fils vs 4 Fils (0–10 V)
- Convertisseur Tension vers 4–20 mA (AOP + Transistor)
- Pont Diviseur NTC + Suiveur AOP & Filtre RC