IEC 60381-1NAMUR NE 432-wire twisted shielded pair

Boucle de Courant 4–20 mA 2 Fils & Récepteur Protégé

4–20 mA Live-Zero + NAMUR NE 43 · 12–36 V DC (24 V nom)

Une boucle 4–20 mA 2 fils alimente le transmetteur et transporte la mesure sur la même paire. Une résistance 250 Ω (1–5 V) avec filtre RC et clamp Schottky protège l’ADC en toute sécurité.

50.0% Scale · 12.00 mA → 3.000 V (Margin +10.42 V)

Constant current flows identically through +Vs → cable → transmitter → cable → 250 Ω sense resistor → 0 V. Cable drop (0.08 V) introduces 0.00% signal error!

Courant normalAlerte / ÉcrêtageDéfaut / SurintensitéVitesse ∝ |I|
Loop PSU+24.0 V0 V (COM)Precision Receiver + Clamp + ADC12.00 mACable Drop: 0.08 V2-Wire Tx50%20.92 VOPEN LOOP 0 mATX SHORT / 24V DIRECT!250 Ω3.00 V10 kΩ100 nFBAT54SPLC / ADC3.00 VOKFLT0 mA Open≤3.6 mA NE 43 Low4.0 – 20.0 mA (0–100% Live-Zero Span)≥21 mA NE 43 High

Actual Loop Current (I)

12.00 mA

Sense Voltage (VRs → VADC)

3.00 → 3.00 V

Transmitter Terminal (Margin)

20.92 (+10.42) V

Sense Resistor Power (PRs)

36 mW

2-Wire Transmitter RegulationREGULATING OK
NAMUR NE 43 StatusNORMAL (4–20 mA)
ADC Protection Clamp DiodeSTANDBY (Reverse-Biased)
HART Modem CompatibilityCOMPATIBLE (≥230 Ω)
V

Standard process loop supply is 24 V DC.

mA

4 mA = 0%, 12 mA = 50%, 20 mA = 100%; NAMUR NE 43 fault <3.6 or >21 mA.

Ω

250 Ω → 1–5 V (HART compatible); 150 Ω → 0.6–3.0 V (3.3 V ADC); 500 Ω → 2–10 V.

V

Minimum terminal voltage the 2-wire transmitter needs to regulate (typically 10–12 V).

m

Long runs increase cable drop (I × R_cable), reducing transmitter voltage margin.

Préréglages :

Formules pas à pas en direct

1. Transmitter terminal voltage & margin

V_tx = V_s − I · (R_s + R_cable), Margin = V_tx − V_min = 24.0 − 0.0120 × (250 + 6.90)

⇒ 20.92 V (Margin +10.42 V)

2. Receiver sense voltage

V_Rs = I · R_s = 0.0120 A × 250 Ω

⇒ 3.000 V → ADC 3.00 V

3. Max allowed loop resistance at 22 mA

R_s(max) = (V_s − V_min) / 0.022 − R_cable = (24.0 − 10.5) / 0.022 − 6.90

⇒ 607 Ω

Nomenclature dynamique (BOM)

Réf.ComposantCalibrage calculéÉtat
RsPrecision Current-Sense Resistor250 Ω ±0.1%, ≤25 ppm/°C, ≥ 0.5 WOK
TVS1Bidirectional Loop Surge TVSSMBJ30CA / SMBJ36CA across loop terminalsOK
R1/D1ADC Input RC Filter & Schottky Clamp10 kΩ + 100 nF (fc ≈ 159 Hz) + BAT54S to 5.0 VOK

1. Présentation & principe de fonctionnement

The 2-wire 4–20 mA current loop is the undisputed backbone of industrial process instrumentation. A single twisted pair supplies operating power to the field transmitter AND carries the continuous measurement back to the PLC/DCS or microcontroller ADC.

Because Kirchhoff’s current law guarantees identical current everywhere in a series loop, long cable resistance (even hundreds of meters) causes ZERO signal accuracy error as long as the power supply leaves enough compliance voltage (Vtx ≥ Vmin) for the transmitter.

Live-Zero (4 mA) & NAMUR NE 43 Diagnostics: Using 4 mA for 0% scale powers the transmitter electronics AND lets the receiver immediately distinguish a real 0% reading (4.00 mA → 1.00 V on 250 Ω) from a broken wire (0.00 mA → 0.00 V). Fault bands < 3.6 mA or > 21.0 mA convey smart transmitter self-diagnostics.

Precision Receiver & ADC Protection: A 0.1% low-tempco sense resistor converts current to voltage (250 Ω → 1–5 V for 5 V ADCs & HART compatibility; 150 Ω → 0.6–3.0 V for 3.3 V MCUs). A 10 kΩ series resistor + 100 nF RC filter + BAT54S Schottky clamp protects the ADC pin if a field technician accidentally applies +24 V directly across Rs!

Compliance Voltage Budget (size at 22 mA!): Always verify Vs − 0.022 × (Rs + Rcable) ≥ Vmin_tx. If the loop starves of voltage, the transmitter clips below 20 mA, silently flattening high readings!

Boucle de Courant 4–20 mA 2 Fils & Récepteur Protégé — SensorCatalog
Boucle 4–20 mA & ProtectionPNG 1200×630

2. Step-by-step: Designing & wiring a rock-solid 4–20 mA loop receiver

  1. 1Select sense resistor Rs for your ADC full-scale & HART needs

    Choose 250 Ω (±0.1%, ≤25 ppm/°C, ≥0.5 W) for 1–5 V PLC/5 V ADC inputs and HART modem compatibility (≥230 Ω required). Choose 150 Ω (0.6–3.0 V) or 120 Ω (0.48–2.4 V) for 3.3 V MCUs so 22 mA fault currents stay under 3.3 V.

  2. 2Verify 22 mA compliance voltage margin

    Calculate Vtx = Vs − 0.022 × (Rs + Rcable). Confirm Vtx exceeds the transmitter minimum lift-off voltage (typically 10–12 V) by at least 2 V across the coldest operating temperature.

  3. 3Add loop surge TVS + 10 kΩ / 100 nF RC filter + Schottky ADC clamp

    Place a bidirectional SMBJ30CA TVS across the field terminals, then feed the voltage across Rs through a 10 kΩ series resistor and 100 nF capacitor (fc ≈ 159 Hz) with a BAT54S Schottky clamp to the ADC supply rail.

  4. 4Commission with 4 mA / 12 mA / 20 mA & open-loop checks

    Inject 4.00 mA (0%), 12.00 mA (50%), and 20.00 mA (100%) using a loop calibrator; confirm ADC counts match linearly, then disconnect one wire to confirm software raises a Wire-Break alarm below 3.6 mA.

3. Dépannage terrain & mesures au multimètre

SymptômeCause racineContrôle multimètreAction corrective
Reading tracks accurately up to 75% then flattens/clipsLoop compliance voltage starvation (Rs too high or Vs too low)Measure DC voltage directly across transmitter + and − terminals at high outputLower Rs (e.g. 500 Ω → 250 Ω) or raise loop power supply to 24–28 V
Sense resistor overheats or burns out during field wiring24 V applied directly across 250 Ω Rs (96 mA → 2.3 W on a 0.25 W resistor!)Inspect Rs value with ohmmeter; check if series PTC fuse (30–50 mA) is installedAdd a 30–50 mA resettable PTC / 25 mA current-limiter diode in series + ≥1 W Rs
50/60 Hz hum or noisy readings on long cable runsGround loop (shield grounded at both ends) or missing RC anti-aliasing filterLift shield at field transmitter end (single-point ground at PLC cabinet only)Use single-point shield ground, twisted pair, and 10 kΩ / 100 nF RC filter

4. Questions fréquentes (FAQ)

Why is 250 Ω the universal sense resistor for 4–20 mA loops?

250 Ω converts 4–20 mA into a clean 1.00–5.00 V range (5× integer scaling) while also satisfying the HART protocol minimum 230 Ω loop impedance required for FSK digital communication.

What sense resistor should I use for a 3.3 V ADC (ESP32 / STM32)?

Use 150 Ω (0.60–3.00 V for 4–20 mA, 3.30 V at 22 mA NE 43 high fault) or 120 Ω (0.48–2.40 V) for extra headroom. Always add a 10 kΩ series resistor and BAT54S Schottky clamp to 3.3 V to survive a 24 V miswire.

Can I connect two receivers (e.g. PLC + panel meter) to one 4–20 mA loop?

Yes, wire them in SERIES (never in parallel!) and verify that the combined loop resistance (Rs1 + Rs2 + Rcable) still leaves Vtx ≥ Vmin at 22 mA. Watch out for ground loops if both receivers tie (−) to chassis ground — use an isolator if so.

Why doesn’t cable length reduce the accuracy of a 4–20 mA signal?

Because the transmitter is an active closed-loop current regulator: it reduces its own internal transistor drop to compensate for extra cable drop, keeping exact loop current flowing through Rs until voltage headroom hits zero.

How do I measure 4–20 mA current without breaking the loop?

Either measure DC voltage across the known 250 Ω sense resistor (I = V / 250), use the transmitter’s dedicated TEST+ / TEST− diode test terminals, or clamp on a milliamp process clamp meter.

What wattage rating should my 250 Ω sense resistor have?

At 20 mA, dissipation is only 0.10 W (0.12 W at 22 mA), so a 0.25 W or 0.5 W thin-film resistor works in normal operation. However, a 24 V miswire puts 2.3 W across 250 Ω — pair a ≥0.5–1 W precision resistor with a series 30–50 mA current limiter or PTC fuse.