1. Panoramica tecnica e principio di funzionamento
The 2-wire 4–20 mA current loop is the undisputed backbone of industrial process instrumentation. A single twisted pair supplies operating power to the field transmitter AND carries the continuous measurement back to the PLC/DCS or microcontroller ADC.
Because Kirchhoff’s current law guarantees identical current everywhere in a series loop, long cable resistance (even hundreds of meters) causes ZERO signal accuracy error as long as the power supply leaves enough compliance voltage (Vtx ≥ Vmin) for the transmitter.
Live-Zero (4 mA) & NAMUR NE 43 Diagnostics: Using 4 mA for 0% scale powers the transmitter electronics AND lets the receiver immediately distinguish a real 0% reading (4.00 mA → 1.00 V on 250 Ω) from a broken wire (0.00 mA → 0.00 V). Fault bands < 3.6 mA or > 21.0 mA convey smart transmitter self-diagnostics.
Precision Receiver & ADC Protection: A 0.1% low-tempco sense resistor converts current to voltage (250 Ω → 1–5 V for 5 V ADCs & HART compatibility; 150 Ω → 0.6–3.0 V for 3.3 V MCUs). A 10 kΩ series resistor + 100 nF RC filter + BAT54S Schottky clamp protects the ADC pin if a field technician accidentally applies +24 V directly across Rs!
Compliance Voltage Budget (size at 22 mA!): Always verify Vs − 0.022 × (Rs + Rcable) ≥ Vmin_tx. If the loop starves of voltage, the transmitter clips below 20 mA, silently flattening high readings!

2. Step-by-step: Designing & wiring a rock-solid 4–20 mA loop receiver
1Select sense resistor Rs for your ADC full-scale & HART needs
Choose 250 Ω (±0.1%, ≤25 ppm/°C, ≥0.5 W) for 1–5 V PLC/5 V ADC inputs and HART modem compatibility (≥230 Ω required). Choose 150 Ω (0.6–3.0 V) or 120 Ω (0.48–2.4 V) for 3.3 V MCUs so 22 mA fault currents stay under 3.3 V.
2Verify 22 mA compliance voltage margin
Calculate Vtx = Vs − 0.022 × (Rs + Rcable). Confirm Vtx exceeds the transmitter minimum lift-off voltage (typically 10–12 V) by at least 2 V across the coldest operating temperature.
3Add loop surge TVS + 10 kΩ / 100 nF RC filter + Schottky ADC clamp
Place a bidirectional SMBJ30CA TVS across the field terminals, then feed the voltage across Rs through a 10 kΩ series resistor and 100 nF capacitor (fc ≈ 159 Hz) with a BAT54S Schottky clamp to the ADC supply rail.
4Commission with 4 mA / 12 mA / 20 mA & open-loop checks
Inject 4.00 mA (0%), 12.00 mA (50%), and 20.00 mA (100%) using a loop calibrator; confirm ADC counts match linearly, then disconnect one wire to confirm software raises a Wire-Break alarm below 3.6 mA.
3. Ricerca guasti sul campo con multimetro
| Sintomo | Causa principale | Verifica multimetro | Soluzione |
|---|---|---|---|
| Reading tracks accurately up to 75% then flattens/clips | Loop compliance voltage starvation (Rs too high or Vs too low) | Measure DC voltage directly across transmitter + and − terminals at high output | Lower Rs (e.g. 500 Ω → 250 Ω) or raise loop power supply to 24–28 V |
| Sense resistor overheats or burns out during field wiring | 24 V applied directly across 250 Ω Rs (96 mA → 2.3 W on a 0.25 W resistor!) | Inspect Rs value with ohmmeter; check if series PTC fuse (30–50 mA) is installed | Add a 30–50 mA resettable PTC / 25 mA current-limiter diode in series + ≥1 W Rs |
| 50/60 Hz hum or noisy readings on long cable runs | Ground loop (shield grounded at both ends) or missing RC anti-aliasing filter | Lift shield at field transmitter end (single-point ground at PLC cabinet only) | Use single-point shield ground, twisted pair, and 10 kΩ / 100 nF RC filter |
4. Domande frequenti (FAQ)
Why is 250 Ω the universal sense resistor for 4–20 mA loops?
250 Ω converts 4–20 mA into a clean 1.00–5.00 V range (5× integer scaling) while also satisfying the HART protocol minimum 230 Ω loop impedance required for FSK digital communication.
What sense resistor should I use for a 3.3 V ADC (ESP32 / STM32)?
Use 150 Ω (0.60–3.00 V for 4–20 mA, 3.30 V at 22 mA NE 43 high fault) or 120 Ω (0.48–2.40 V) for extra headroom. Always add a 10 kΩ series resistor and BAT54S Schottky clamp to 3.3 V to survive a 24 V miswire.
Can I connect two receivers (e.g. PLC + panel meter) to one 4–20 mA loop?
Yes, wire them in SERIES (never in parallel!) and verify that the combined loop resistance (Rs1 + Rs2 + Rcable) still leaves Vtx ≥ Vmin at 22 mA. Watch out for ground loops if both receivers tie (−) to chassis ground — use an isolator if so.
Why doesn’t cable length reduce the accuracy of a 4–20 mA signal?
Because the transmitter is an active closed-loop current regulator: it reduces its own internal transistor drop to compensate for extra cable drop, keeping exact loop current flowing through Rs until voltage headroom hits zero.
How do I measure 4–20 mA current without breaking the loop?
Either measure DC voltage across the known 250 Ω sense resistor (I = V / 250), use the transmitter’s dedicated TEST+ / TEST− diode test terminals, or clamp on a milliamp process clamp meter.
What wattage rating should my 250 Ω sense resistor have?
At 20 mA, dissipation is only 0.10 W (0.12 W at 22 mA), so a 0.25 W or 0.5 W thin-film resistor works in normal operation. However, a 24 V miswire puts 2.3 W across 250 Ω — pair a ≥0.5–1 W precision resistor with a series 30–50 mA current limiter or PTC fuse.
5. Calcolatori correlati, guide e altri circuiti
- Convertitore 4–20 mA
- Alimentazione del loop 4–20 mA
- Calcolatore di scalatura analogica PLC
- Calcolatore di risoluzione ADC
- 4–20 mA vs 0–10 V: quale segnale analogico scegliere?
- Trasmettitore Analogico Attivo 3 Fili vs 4 Fili (0–10 V)
- Trasmettitore Tensione a 4–20 mA (Op-Amp + Transistor)
- Scalatura Analogica ±10 V / 0–10 V con Protezione 24 V
- Uscita Sensore PNP 3 Fili (Sourcing) — Circuito e Simulatore
- Uscita Sensore NPN 3 Fili (Sinking / Open-Collector)
- Circuito NAMUR 2 Fili Sicurezza Intrinseca (IEC 60947-5-6)
- Uscita Push-Pull (HTL/TTL) e Open-Drain — Simulatore