1. Panoramica tecnica e principio di funzionamento
Every 24 V industrial sensor module or PLC expansion board must survive three field realities: reversed power wiring (−24 V), relay/motor inductive surges (+40–60 V), and downstream short circuits. Combining a polymeric PTC fuse, SMBJ28A TVS, and a P-channel MOSFET with a 12 V Zener gate clamp delivers bulletproof protection with millivolt drop.
Why PMOS Beats a Diode: A 1N4007 or Schottky diode wastes 0.5–0.8 V and heats up at high current. A back-wired PMOS (drain to input, source to load) conducts through its 45 mΩ channel during normal polarity (only ~7 mV drop at 150 mA!) yet blocks −24 V completely when reversed.
Mandatory 12 V Zener Gate Clamp: Most PMOS gates rupture above ±20 V! On a 24 V industrial rail (plus 38 V TVS surges), tying Gate directly to GND destroys Q1 immediately. Placing a 12 V Zener between Gate and Source + 100 kΩ to GND locks Vgs safely at −12 V.

2. Step-by-step: Building a bulletproof 24 V sensor power entry stage
1Size PTC I_hold ≥ 1.8× max load to survive 60 °C cabinets
Polymeric PTC fuses derate by ~30% at 60 °C ambient; undersizing causes mysterious random resets.
2Select SMBJ28A TVS (Vrwm = 28 V) after the PTC
Place TVS AFTER the PTC so sustained overvoltage trips the PTC instead of exploding the TVS.
3Orient PMOS Source toward the load and Drain toward input
Verify body diode anode faces Drain so forward power starts conduction and reverse polarity blocks!
4Add 12 V Zener across G–S + 100 kΩ gate resistor
Use a −40 V or −60 V rated PMOS so it survives the ~38–45 V clamping peak of the SMBJ28A.
3. Ricerca guasti sul campo con multimetro
| Sintomo | Causa principale | Verifica multimetro | Soluzione |
|---|---|---|---|
| PMOS shorts out permanently on first 24 V power-up | Missing 12 V Zener clamp — 24 V exceeded PMOS ±20 V Vgs(max) rating | Measure Gate-to-Source resistance (often <10 Ω after gate punch-through) | Install 12 V Zener (BZT52C12) across G–S and 100 kΩ to GND |
4. Domande frequenti (FAQ)
Why put the TVS diode after the PTC instead of before it?
If someone applies a continuous 36 V overvoltage, the TVS conducts heavily; placing the PTC upstream lets the PTC trip and protect the TVS from burning up.
5. Calcolatori correlati, guide e altri circuiti
- Calcolatore di caduta di tensione dell’alimentazione del sensore
- Calcolatore della durata della batteria
- Uscita Sensore PNP 3 Fili (Sourcing) — Circuito e Simulatore
- Uscita Sensore NPN 3 Fili (Sinking / Open-Collector)
- Circuito NAMUR 2 Fili Sicurezza Intrinseca (IEC 60947-5-6)
- Uscita Push-Pull (HTL/TTL) e Open-Drain — Simulatore
- Isolamento Fotoaccoppiatore e Relè con Diodo di Ricircolo
- Contatto Pulito: Antirimbalzo Hardware RC e Corrente di Wetting
- Loop di Corrente 4–20 mA 2 Fili e Ricevitore Protetto
- Trasmettitore Analogico Attivo 3 Fili vs 4 Fili (0–10 V)
- Trasmettitore Tensione a 4–20 mA (Op-Amp + Transistor)
- Partitore NTC + Buffer Op-Amp e Filtro RC