1. Überblick & Funktionsprinzip
NAMUR (standardized in IEC 60947-5-6 / EN 60947-5-6) is the gold-standard 2-wire proximity sensor circuit for explosive hazardous areas (ATEX / IECEx Zone 0, 1, 20, 21). Instead of a switching transistor inside the hazardous zone, the sensor acts as a low-energy variable resistor.
All switching amplification and relay contacts live safely outside the explosive zone inside an Ex ia isolated switch amplifier barrier (nominally 8.2 V DC open-circuit voltage through a 1000 Ω series resistor), capping worst-case short-circuit power to ~17 mW — incapable of creating an ignition spark.
Four distinct current windows encode both process state AND cable health on just two wires: Wire Break (≤ 0.1 mA), Damped / Target Present (0.1–1.2 mA), Undamped / No Target (2.1–6.5 mA), and Short Circuit (> 6.5 mA).
Built-in hysteresis (~1.2 to 2.1 mA switching band, nominal switch point ~1.55 mA with ~0.2 mA hysteresis) keeps the safe-area relay from chattering as a valve stem or turbine blade passes slowly through the sensing zone.
Line Fault Detection (LFD): Unlike 3-wire PNP/NPN sensors that cannot tell the difference between "no target" and a severed wire, a NAMUR circuit always maintains a live current (0.1–6.5 mA) when healthy — immediately lighting a red LFD fault LED if the field cable opens or shorts.

2. Step-by-step: Commissioning a NAMUR sensor & Ex ia switch amplifier
1Verify Ex entity parameters (Uo ≤ Ui, Io ≤ Ii, Po ≤ Pi, Co/Lo)
Before installation in Zone 0/1, confirm the barrier entity ratings match the sensor and cable: Uo ≤ Ui, Io ≤ Ii, Po ≤ Pi, and total cable + sensor capacitance/inductance stays below Co and Lo.
2Wire the 2-wire sensor with blue-jacketed IS cable
Connect Brown (+) and Blue (−) of the NAMUR sensor to the barrier hazardous-side input terminals using light-blue intrinsically safe cable separated from non-IS power cables per IEC 60079-14.
3Enable LFD (Line Fault Detection) & fail-safe relay mode
Set the DIP switches on the switch amplifier to enable LFD and select the safe output direction (normally energized relay that drops out on fault or power loss).
4Test all 4 states (Undamped, Damped, Open, Short)
Verify with a series milliammeter (safe-area bench check): >2.1 mA undamped (Yellow ON), <1.2 mA damped (Yellow OFF), open lead → Red LFD ON, shorted leads → Red LFD ON (~8.2 mA).
3. Fehlersuche & Multimeter-Diagnose
| Symptom | Ursache | Multimeter-Prüfung | Abhilfe |
|---|---|---|---|
| Red LFD LED stays ON constantly after installation | Reversed polarity on 2-wire NAMUR sensor, open terminal, or pinched short | Check terminal voltage at barrier: ~8.2 V = open/reversed; ~0 V = short circuit | Swap Brown/Blue leads if reversed, tighten terminal block, or clear moisture short |
| Sensor fails to switch even though metal target touches face | Connected a mechanical dry contact without NAMUR resistor kit (10 kΩ || 1 kΩ) | Measure current: dry contact toggles between 0 mA (Break!) and 8.2 mA (Short!) | Add standard NAMUR resistor kit (10 kΩ parallel + 1 kΩ series) across dry contact |
4. Häufige technische Fragen (FAQ)
Can I connect a NAMUR sensor directly to a standard 24 V PLC digital input?
No! Connecting 24 V directly will destroy an 8.2 V NAMUR sensor and violates hazardous-area Ex certification. Always wire NAMUR sensors through a dedicated IEC 60947-5-6 switch amplifier or certified NAMUR PLC module.
Why is the NAMUR standard supply exactly 8.2 V with 1000 Ω resistance?
At 8.2 V and 1 kΩ, maximum short-circuit current is 8.2 mA and maximum matched-load power is 8.2² / (4 × 1000) = 16.8 mW — orders of magnitude below the minimum ignition energy of even Group IIC hydrogen/acetylene atmospheres.
How can I connect a standard mechanical limit switch to a NAMUR barrier with LFD?
Wire a 10 kΩ resistor in parallel with the switch contact and a 1 kΩ (or 2.2 kΩ) resistor in series. When the contact is open, ~0.75 mA flows (Damped/OFF, cable healthy); when closed, ~4.1 mA flows (Undamped/ON); open wire or short still trips LFD!
Does long cable length break NAMUR switching thresholds?
Because the circuit already has 1000 Ω + 2000 Ω = 3000 Ω total resistance, 100 m of 0.5 mm² pair adds only ~6.9 Ω (<0.25% current shift). Keep total loop resistance below 50–100 Ω per barrier datasheet and always check cable capacitance Co.
What is the difference between NAMUR and 4–20 mA loops?
NAMUR (IEC 60947-5-6) is a discrete ON/OFF switch interface at 8.2 V using 0.1 / 1.2 / 2.1 / 6.5 mA windows. 4–20 mA (IEC 60381-1) is a continuous analog process loop at 24 V measuring pressure, level, temperature, or flow.
Are NAMUR sensors polarity sensitive?
Yes. Standard DC NAMUR sensors have a Brown (+) and Blue (−) wire. Reversing polarity blocks current flow (<0.1 mA) and triggers the barrier Wire-Break LFD alarm, though it normally does not damage the sensor.
5. Zugehörige Rechner, Leitfäden & weitere Schaltungen
- Ex-Kennzeichnung entschlüsseln
- Speisespannung und Bürde für 4–20 mA
- NAMUR vs. PNP vs. NPN: Schaltausgänge, Verdrahtung & CSV-Referenz
- ATEX / IECEx vs. NEC Class/Division: Ex-Zonen-Querverweis & CSV
- PNP-Schaltausgang (3-Leiter, Plus-schaltend) — Schaltung & Simulator
- NPN-Schaltausgang (3-Leiter, Minus-schaltend) — Schaltung & Simulator
- Gegentakt (HTL/TTL Push-Pull) & Open-Drain Sensorausgang
- Optokoppler-Trennung & Relais-Freilaufdiode (Sensoreingang)
- 24-V-Sensoreingangsschutz (PMOS-Verpolschutz, TVS & PTC)
- Potentialfreier Kontakt: Hardware-Entprellung & Benetzungsstrom
- 2-Leiter 4–20 mA Stromschleife & geschützter Empfänger
- 3-Leiter vs 4-Leiter Aktiver Analog-Messumformer (0–10 V)
- Spannung-zu-4–20 mA Stromsender (OPV + Längstransistor)
- NTC-Spannungsteiler + OPV-Impedanzwandler & RC-Filter