IEC 60947-5-6IEC 60079-112-wire (BN +, BU −, Blue IS cable)

NAMUR 2선식 본질안전 방폭 센서 회로 (IEC 60947-5-6)

4-Window Analog Current (Ex ia) · 8.2 V DC nom via 1000 Ω barrier

NAMUR 센서(IEC 60947-5-6)는 8.2 V / 1 kΩ Ex ia 스위치 앰프와 2선으로 연결되어 감지 상태(>2.1 mA / <1.2 mA)와 단선(<0.1 mA)·단락(>6.5 mA)을 동시에 진단합니다.

UNDAMPED (2.73 mA > 2.1 mA) — Amplifier Relay ON · LFD Normal

Current sits cleanly in the IEC 60947-5-6 High window (2.1–6.5 mA). Hazardous-area power is intrinsically safe (Po = 16.8 mW).

정상 전류 흐름경고 / 클램프고장 / 과전류속도 ∝ 전류 |I|
HAZARDOUS AREA (Zone 0 / 1 · Ex ia)SAFE AREA: NAMUR Ex ia Switch AmplifierDAMPINGNAMUR SensorIEC 60947-5-65.46 VEx ia Source & LFD8.2 V1000 ΩBlue IS Cable (+)2.73 mAR_cab = 3.45 ΩBREAK <0.1mASHORT >6.5mAHIGH (>2.1 mA)PWROUTLFDOutput RelayCLOSEDTo PLC / SIS≤0.1mA Break0.1–1.2mA Damped1.2–2.1 Hyst2.1–6.5mA Undamped>6.5mA Short

NAMUR Loop Current (I)

2.73 mA

Sensor Terminal Voltage (Vs)

5.46 V

IEC 60947-5-6 Window

UNDAMPED

Max Barrier Output Power (Po)

16.8 mW

Barrier Power LED (Green)ON · Ex ia OK
Output Relay LED (Yellow)ENERGIZED (NO Closed)
Line Fault LED (Red LFD)OFF (Cable Healthy)
Hazardous Area EnergySAFE (16.8 mW Ex ia)
V

IEC 60947-5-6 nominal supply is 8.2 V DC (range 7.5–9.0 V).

Ω

IEC 60947-5-6 standard source impedance is 1000 Ω (±10%).

Ω

Undamped ~1.5–2.2 kΩ (>2.1 mA); Damped ~7–10 kΩ (<1.2 mA).

m

0.5 mm² twisted pair (34.5 mΩ/m per wire).

프리셋:

실시간 단계별 수식

1. NAMUR loop current

I = U_o / (R_i + R_cable + R_sensor) = 8.2 / (1000 + 3.45 + 2000)

⇒ 2.73 mA

2. Intrinsic safety max fault power

P_o = U_o² / (4 · R_i) = 8.2² / (4 × 1000)

⇒ 16.8 mW (Ex ia Safe)

3. IEC 60947-5-6 4-window decoder

≤0.1 Break | 0.1–1.2 Low | 2.1–6.5 High | >6.5 Short = I = 2.73 mA

⇒ UNDAMPED

동적 부품 선정 및 BOM

부호부품계산 정격상태
BAR1NAMUR Isolated Switch Amplifier (Ex ia)Uo = 8.2 V, Ri = 1000 Ω, LFD enabledOK
S12-Wire NAMUR Sensor (IEC 60947-5-6)BN (+), BU (−) — Blue IS jacket cableOK
CAB1Blue Intrinsically Safe Twisted Pair50 m, 0.5 mm² (R_loop = 3.45 Ω)OK

1. 회로 개요 및 동작 원리

NAMUR (standardized in IEC 60947-5-6 / EN 60947-5-6) is the gold-standard 2-wire proximity sensor circuit for explosive hazardous areas (ATEX / IECEx Zone 0, 1, 20, 21). Instead of a switching transistor inside the hazardous zone, the sensor acts as a low-energy variable resistor.

All switching amplification and relay contacts live safely outside the explosive zone inside an Ex ia isolated switch amplifier barrier (nominally 8.2 V DC open-circuit voltage through a 1000 Ω series resistor), capping worst-case short-circuit power to ~17 mW — incapable of creating an ignition spark.

Four distinct current windows encode both process state AND cable health on just two wires: Wire Break (≤ 0.1 mA), Damped / Target Present (0.1–1.2 mA), Undamped / No Target (2.1–6.5 mA), and Short Circuit (> 6.5 mA).

Built-in hysteresis (~1.2 to 2.1 mA switching band, nominal switch point ~1.55 mA with ~0.2 mA hysteresis) keeps the safe-area relay from chattering as a valve stem or turbine blade passes slowly through the sensing zone.

Line Fault Detection (LFD): Unlike 3-wire PNP/NPN sensors that cannot tell the difference between "no target" and a severed wire, a NAMUR circuit always maintains a live current (0.1–6.5 mA) when healthy — immediately lighting a red LFD fault LED if the field cable opens or shorts.

NAMUR 2선식 본질안전 방폭 센서 회로 (IEC 60947-5-6) — SensorCatalog
NAMUR 본질안전 회로PNG 1200×630

2. Step-by-step: Commissioning a NAMUR sensor & Ex ia switch amplifier

  1. 1Verify Ex entity parameters (Uo ≤ Ui, Io ≤ Ii, Po ≤ Pi, Co/Lo)

    Before installation in Zone 0/1, confirm the barrier entity ratings match the sensor and cable: Uo ≤ Ui, Io ≤ Ii, Po ≤ Pi, and total cable + sensor capacitance/inductance stays below Co and Lo.

  2. 2Wire the 2-wire sensor with blue-jacketed IS cable

    Connect Brown (+) and Blue (−) of the NAMUR sensor to the barrier hazardous-side input terminals using light-blue intrinsically safe cable separated from non-IS power cables per IEC 60079-14.

  3. 3Enable LFD (Line Fault Detection) & fail-safe relay mode

    Set the DIP switches on the switch amplifier to enable LFD and select the safe output direction (normally energized relay that drops out on fault or power loss).

  4. 4Test all 4 states (Undamped, Damped, Open, Short)

    Verify with a series milliammeter (safe-area bench check): >2.1 mA undamped (Yellow ON), <1.2 mA damped (Yellow OFF), open lead → Red LFD ON, shorted leads → Red LFD ON (~8.2 mA).

3. 현장 트러블슈팅 및 멀티미터 점검

증상근본 원인멀티미터 점검조치 방법
Red LFD LED stays ON constantly after installationReversed polarity on 2-wire NAMUR sensor, open terminal, or pinched shortCheck terminal voltage at barrier: ~8.2 V = open/reversed; ~0 V = short circuitSwap Brown/Blue leads if reversed, tighten terminal block, or clear moisture short
Sensor fails to switch even though metal target touches faceConnected a mechanical dry contact without NAMUR resistor kit (10 kΩ || 1 kΩ)Measure current: dry contact toggles between 0 mA (Break!) and 8.2 mA (Short!)Add standard NAMUR resistor kit (10 kΩ parallel + 1 kΩ series) across dry contact

4. 자주 묻는 엔지니어링 질문 (FAQ)

Can I connect a NAMUR sensor directly to a standard 24 V PLC digital input?

No! Connecting 24 V directly will destroy an 8.2 V NAMUR sensor and violates hazardous-area Ex certification. Always wire NAMUR sensors through a dedicated IEC 60947-5-6 switch amplifier or certified NAMUR PLC module.

Why is the NAMUR standard supply exactly 8.2 V with 1000 Ω resistance?

At 8.2 V and 1 kΩ, maximum short-circuit current is 8.2 mA and maximum matched-load power is 8.2² / (4 × 1000) = 16.8 mW — orders of magnitude below the minimum ignition energy of even Group IIC hydrogen/acetylene atmospheres.

How can I connect a standard mechanical limit switch to a NAMUR barrier with LFD?

Wire a 10 kΩ resistor in parallel with the switch contact and a 1 kΩ (or 2.2 kΩ) resistor in series. When the contact is open, ~0.75 mA flows (Damped/OFF, cable healthy); when closed, ~4.1 mA flows (Undamped/ON); open wire or short still trips LFD!

Does long cable length break NAMUR switching thresholds?

Because the circuit already has 1000 Ω + 2000 Ω = 3000 Ω total resistance, 100 m of 0.5 mm² pair adds only ~6.9 Ω (<0.25% current shift). Keep total loop resistance below 50–100 Ω per barrier datasheet and always check cable capacitance Co.

What is the difference between NAMUR and 4–20 mA loops?

NAMUR (IEC 60947-5-6) is a discrete ON/OFF switch interface at 8.2 V using 0.1 / 1.2 / 2.1 / 6.5 mA windows. 4–20 mA (IEC 60381-1) is a continuous analog process loop at 24 V measuring pressure, level, temperature, or flow.

Are NAMUR sensors polarity sensitive?

Yes. Standard DC NAMUR sensors have a Brown (+) and Blue (−) wire. Reversing polarity blocks current flow (<0.1 mA) and triggers the barrier Wire-Break LFD alarm, though it normally does not damage the sensor.