Type K thermocouple accuracy at 500 °C

What IEC 60584-1 allows a type K thermocouple at 500 °C, class by class, and what the rest of the measurement adds.

Tolerance by class

ClassTolerance (°C)% of reading
1±2.00±0.40 %
2±3.75±0.75 %
3not defined at this temperature

At 500 °C

EMF
20.644 mVcold junction at 0 °C
Sensitivity
42.63 µV/KNIST ITS-90
Cold-junction factor
0.950a 1 K error at 25 °C terminals reads as this many K

Example: the whole measurement

TermAssumptionError
Sensor toleranceClass 1±2.000 K
Cold junction±0.5 K, 25 °C±0.475 K
Transmitter input±0.5 K±0.500 K
Analog output±0.03 % × 1000 K±0.300 K
Ambient effect±0.1 % / 10 K × 20 K±2.000 K
Total probable errorRSS±2.93 K
Worst caseΣ±5.28 K

An example with typical datasheet figures, not a statement about any product. Enter your own values in the calculator.

Open this example in the error calculator

How the tolerance is defined

IEC 60584-1 gives each class as a fixed value or a fraction of |t|, whichever is larger, within a temperature range that depends on the type. The table is that rule evaluated at 500 °C. The limits apply to new thermocouple wire as supplied; drift in service is not included.