Type K thermocouple accuracy at 200 °C

What IEC 60584-1 allows a type K thermocouple at 200 °C, class by class, and what the rest of the measurement adds.

Tolerance by class

ClassTolerance (°C)% of reading
1±1.50±0.75 %
2±2.50±1.25 %
3not defined at this temperature

At 200 °C

EMF
8.138 mVcold junction at 0 °C
Sensitivity
39.97 µV/KNIST ITS-90
Cold-junction factor
1.014a 1 K error at 25 °C terminals reads as this many K

Example: the whole measurement

TermAssumptionError
Sensor toleranceClass 1±1.500 K
Cold junction±0.5 K, 25 °C±0.507 K
Transmitter input±0.5 K±0.500 K
Analog output±0.03 % × 400 K±0.120 K
Ambient effect±0.1 % / 10 K × 20 K±0.800 K
Total probable errorRSS±1.85 K
Worst caseΣ±3.43 K

An example with typical datasheet figures, not a statement about any product. Enter your own values in the calculator.

Open this example in the error calculator

How the tolerance is defined

IEC 60584-1 gives each class as a fixed value or a fraction of |t|, whichever is larger, within a temperature range that depends on the type. The table is that rule evaluated at 200 °C. The limits apply to new thermocouple wire as supplied; drift in service is not included.