1. Überblick & Funktionsprinzip
Thermocouples (Type K, J, T, E, N, R, S, B per IEC 60584-1) are self-powered rugged sensors capable of measuring up to 1372 °C (Type K) and 1768 °C (Type S) — yet their front-end circuit is deceptively subtle because the signal is only ~41 µV/°C and measures temperature DIFFERENCE, never absolute temperature.
A production-grade thermocouple circuit ALWAYS requires three essential blocks: an isothermal Cold-Junction Compensation (CJC) temperature sensor thermally bonded to the screw terminal block, a symmetric differential + common-mode EMI filter, and high-value pull-up/pull-down resistors (1–10 MΩ) providing both DC common-mode bias and fail-safe Open-Thermocouple burnout detection.
CJC Must Be Added in Millivolts (NOT Degrees!): Because Type K Seebeck sensitivity is nonlinear across temperature, never simply add T_cj to the uncompensated temperature. Always compute E_total = E_measured + E(T_cj) in millivolts first, then invert the NIST ITS-90 polynomial to obtain exact T_hot!
Common-Mode Bias & Open-TC Burnout: A floating thermocouple has no path for op-amp/ADC input bias currents, causing the inputs to rail out. Adding symmetric 10 MΩ pull-up (on TC+) and 10 MΩ pull-down (on TC−) holds the thermocouple safely at Vcc/2 while intact — and snaps differential voltage hard to +Vcc the instant the welded bead burns open!

2. Step-by-step: Designing an accurate, fail-safe Type K thermocouple front-end
1Use matching thermocouple extension cable all the way to the PCB terminal
Never splice plain copper wire in the middle of a thermocouple run — every copper-to-alloy splice creates an uncompensated parasitic thermocouple junction! Keep the transition right at your isothermal terminal block.
2Thermally bond the CJC sensor directly beside the screw terminals
Mount a precision digital sensor (TMP117 / MAX31856 internal sensor) on a solid copper island touching the TC terminal pads, shielded from LDOs, relays, and airflow drafts — every 1 °C gradient between terminal and CJC becomes a 1 °C error!
3Add symmetric EMI filter + 10 MΩ open-TC burnout resistors
Place matched 1 kΩ resistors + 100 nF differential + 2 × 10 nF common-mode C0G caps at the ADC input, plus 10 MΩ pull-up on TC+ and 10 MΩ pull-down on TC− (or use integrated burnout current sources in MAX31856 / ADS1118).
4Verify polarity (IEC Green+/White− vs ANSI Yellow+/Red−) and ice-point test
Warm the probe tip with your fingers: reading MUST rise (if it drops, leads are swapped!). Dip into stirred crushed-ice water to confirm 0.0 ± 1.0 °C before oven commissioning.
3. Fehlersuche & Multimeter-Diagnose
| Symptom | Ursache | Multimeter-Prüfung | Abhilfe |
|---|---|---|---|
| Reading drops negative as the furnace heats up | Thermocouple polarity reversed (common trap: ANSI Red wire is NEGATIVE!) | Warm the junction with a lighter/hairdryer and check if mV goes negative | Swap the two thermocouple leads at the terminal block (check color code chart) |
| Temperature reads consistently 20–45 °C too low across all temperatures | Cold-junction compensation (CJC) disabled in firmware/PLC, or plain copper wire used for extension | Compare the error magnitude against the cabinet ambient temperature | Enable CJC in software/module and replace copper extension runs with matching Type K cable |
4. Häufige technische Fragen (FAQ)
Why is the RED wire NEGATIVE on ANSI thermocouples?
ANSI MC96.1 standardized Red as the negative leg across ALL thermocouple types (e.g. Type K is Yellow+ / Red−, Type J is White+ / Red−). IEC 60584-3 uses White as the negative leg (Type K is Green+ / White−). Always verify which standard your cable follows!
Can I use plain copper wire to extend a thermocouple over 20 meters?
Never! Switching from thermocouple alloy to copper at a warm field junction box shifts the cold junction out to that unmeasured box, introducing an error equal to the temperature difference between the field box and your cabinet. Use matching extension cable or mount a head-mounted 4–20 mA transmitter.
Why must grounded-tip thermocouples use an isolated front-end?
A grounded thermocouple welds the junction directly to the metal sheath for fast response — tying TC− to the furnace/pipe earth. Connecting multiple grounded probes to a non-isolated multi-channel ADC shorts them through earth ground loops!
Do the 10 MΩ burnout bias resistors cause a measurement offset error?
With 10 MΩ pull-up/down on 3.3 V, ~0.165 µA flows through the thermocouple loop resistance (typically 5–50 Ω), producing only 0.8–8 µV — less than 0.02–0.2 °C on Type K! For ultra-long thin probes (>200 Ω), use switched burnout current sources instead.
Why not just add T_cj directly to the raw thermocouple temperature?
Because thermocouple Seebeck slope varies with temperature (e.g. Type K is 39.5 µV/°C at 0 °C, 42.6 µV/°C at 500 °C, and Type B/R/S vary by >2×!). Adding in EMF millivolts first per NIST ITS-90 avoids multi-degree nonlinearity errors.
How do I choose between a Thermocouple, PT100 RTD, and NTC thermistor?
Pick Thermocouples above 500–600 °C, tiny fast-response probes, or extreme vibration. Pick PT100/PT1000 RTDs for ±0.1–0.5 °C industrial accuracy from −200 to +500 °C. Pick NTC thermistors for low-cost, high-sensitivity −40 to +125 °C electronics and battery packs.
5. Zugehörige Rechner, Leitfäden & weitere Schaltungen
- Thermoelement-Rechner
- Thermoelement-Farbcode-Decoder
- Rechner für den Temperaturmessfehler
- Thermoelement vs. RTD (PT100): Welcher Temperatursensor passt?
- NTC-Spannungsteiler + OPV-Impedanzwandler & RC-Filter
- Wheatstone-Messbrücke + Instrumentenverstärker (INA)
- 2-/3-/4-Leiter RTD (PT100 / PT1000) Konstantstrom-Speisung
- Hochohmiges pH-Glaselektroden-Frontend & Guard Ring
- PNP-Schaltausgang (3-Leiter, Plus-schaltend) — Schaltung & Simulator
- NPN-Schaltausgang (3-Leiter, Minus-schaltend) — Schaltung & Simulator
- NAMUR 2-Leiter Eigensicherheits-Schaltung (IEC 60947-5-6)
- 2-Leiter 4–20 mA Stromschleife & geschützter Empfänger