1. Descripción general y principio de funcionamiento
Platinum Resistance Temperature Detectors (PT100 and PT1000 per IEC 60751) deliver unmatched long-term stability (±0.15 °C Class A) from −200 °C to +850 °C — provided the excitation circuit cancels lead-wire resistance and limits self-heating.
Because PT100 changes by only 0.385 Ω per °C, even 1.5 Ω of lead resistance per conductor adds a catastrophic +7.8 °C offset in a 2-wire connection! Understanding 2-wire vs 3-wire dual-IDAC vs 4-wire Kelvin excitation is mandatory for every instrumentation engineer.
4-Wire Kelvin (Gold Standard): Two outer wires force constant current Iexc through the platinum element while two inner high-impedance wires connect straight to the differential ADC (drawing nanoamps). Since I_sense ≈ 0, lead resistance produces ZERO voltage drop — even if all four wires have different resistances!
3-Wire Dual-IDAC (Industrial Workhorse): Two matched constant-current sources (IDAC1 = IDAC2) flow through two identical lead wires, cancelling R_lead1 − R_lead2 = 0 on one fewer copper conductor than 4-wire. Ratiometric wiring through a single precision Rref cancels IDAC drift automatically.

2. Step-by-step: Wiring and sizing a ratiometric PT100 / PT1000 excitation circuit
1Choose 3-wire or 4-wire for PT100 (never 2-wire beyond 1 m!)
For PT100 over any run > 1 m, specify 3-wire (industrial standard) or 4-wire (lab/calibration). If stuck with 2-wire cabling, switching from PT100 to PT1000 cuts lead-wire temperature error by 10× immediately.
2Keep excitation current ≤ 1.0 mA (PT100) or ≤ 0.25 mA (PT1000)
Calculate P = Iexc² × R(T). Keeping dissipation under 0.25 mW ensures self-heating stays below 0.1 °C even in still air (0.5–1.0 mA for PT100; 0.1–0.25 mA for PT1000).
3Use a single low-drift Rref in series for true ratiometric ADC conversion
Route the same excitation current through Rref (402 Ω for PT100, 4.02 kΩ for PT1000, ±0.05%, ≤10 ppm/°C) to generate the ADC’s Vref — making Iexc accuracy and drift cancel out completely!
4Match RC filter resistors symmetrically and verify open/short detection
Keep input filter resistors identical (e.g. 1 kΩ ±0.1%) with C_diff = 100 nF and C_cm = 10 nF C0G, and test open-lead burnout reporting during commissioning.
3. Diagnóstico en campo y pruebas con multímetro
| Síntoma | Causa raíz | Prueba con multímetro | Solución |
|---|---|---|---|
| PT100 reads consistently +3 to +10 °C higher than a calibrated reference | Wired as 2-wire (or 3-wire jumper installed at PLC end instead of sensor end!) | Measure resistance between the two same-colored leads (e.g. Red–Red): must be < 3 Ω | Run true 3rd wire all the way to the RTD probe head, or upgrade to 4-wire |
| 3-wire PT100 still has a ±0.5–1.0 °C offset after wiring properly | Lead-wire resistance mismatch (oxidized terminal block screw on one wire) or IDAC mismatch | Swap the two identical-color leads or enable IDAC chopping in ADS124S08 | Tighten/clean terminals, use matched 3-core cable, or switch to 4-wire Kelvin |
4. Preguntas frecuentes (FAQ)
Why is 4-wire RTD more accurate than 3-wire RTD?
3-wire assumes two lead wires have identical resistance — any oxidized terminal or contact resistance difference creates an uncancelled error. 4-wire Kelvin draws virtually zero current on the sense leads, cancelling lead resistance completely even when wires don’t match.
How do I identify the wires on a standard IEC 60751 3-wire or 4-wire PT100?
Per IEC 60751: 3-wire has 2 Red + 1 White (the two Red leads connect to the same side of the element; Red–Red measures just loop lead resistance ~1 Ω, Red–White measures ~100 Ω at 0 °C). 4-wire has 2 Red + 2 White (one Red+White pair on each side).
Why should PT1000 use lower excitation current than PT100?
Self-heating power is P = I² × R. At the same 1 mA current, a PT1000 dissipates 10× more heat than a PT100 (1.0 mW vs 0.1 mW!), warming itself by ~0.4 °C in air. Dropping Iexc to 0.2 mA cuts PT1000 heat 25× while still producing a clean 200 mV signal!
What is the purpose of Rref in a MAX31865 or ADS124S08 RTD circuit?
Rref turns the circuit into a ratiometric resistance bridge: the ADC measures the ratio V_RTD / V_Rref = R_RTD / R_ref directly, so excitation current drift disappears completely. Only Rref’s own stability matters (use ≤10 ppm/°C).
Can I jumper a 2-wire PT100 to a 3-wire PLC input card?
Yes, jumper the third compensation terminal to one of the two wires at the PLC block so the card won’t fault — BUT understand this provides ZERO lead-wire cancellation (cable resistance still adds full +2·Rlead error).
Why does an RTD read wildly negative or max-scale when a single wire breaks?
With the current path broken, the excitation IDAC drives the input node straight up to its compliance rail (+3.3 V), which exceeds the max valid resistance code and triggers the ADC/PLC Open-RTD fault flag.
5. Calculadoras relacionadas, guías y otros circuitos
- Error por cableado en RTD
- Calculadora PT100 / PT1000
- Calculadora PT1000
- Calculadora del error de medida de temperatura
- PT100 vs PT1000: ¿qué RTD de platino conviene usar?
- Termopar vs RTD (PT100): ¿qué sensor de temperatura elegir?
- Divisor de Tensión NTC + Buffer Op-Amp y Filtro RC
- Puente de Wheatstone + Amplificador de Instrumentación
- Frontal Termopar Tipo K: CJC, Filtro EMI y Detección Rotura
- Frontal Electrodo de Vidrio pH Alta Impedancia y Anillo de Guarda
- Circuito de Salida PNP 3 Hilos (Sourcing) — Simulador
- Circuito de Salida NPN 3 Hilos (Sinking / Colector Abierto)
- Circuito NAMUR 2 Hilos Seguridad Intrínseca (IEC 60947-5-6)
- Lazo de Corriente 4–20 mA 2 Hilos y Receptor Protegido