An AC Current Transformer (CT) such as SCT-013-000 outputs an isolated AC secondary current proportional to mains load current. To sample both half-cycles with a single-supply 3.3 V MCU ADC, you need three essentials: a precision burden resistor R_B, a low-impedance Vref/2 mid-rail bias, and a bidirectional TVS across the secondary to prevent lethal open-circuit high voltage.
Burden Sizing & Crest Factor: Peak secondary current is I_rms × √2 / N. Choose R_B so V_pk = I_sec(pk) × R_B stays below 0.85 × (Vref / 2) to leave margin for non-sinusoidal motor/SMPS current crests.
Why Open-CT Secondary Is Dangerous: A CT forces magnetic flux to drive current; if R_B disconnects, secondary voltage spikes above 100–300 V, arcing across connectors and destroying insulation. A bidirectional SMBJ15CA TVS clamps open-circuit spikes safely.

2. Step-by-step: Interfacing an AC current transformer to a 3.3 V ADC
1Calculate max burden R_B from peak primary current and turns ratio
Use R_B ≤ (Vref / 2 × 0.85) / (I_max × √2 / N) and pick a 1% low-tempco metal-film resistor.
2Build a low-impedance Vref/2 mid-rail bias with 10 µF bypass
Two equal 10 kΩ resistors + 10 µF capacitor give < 0.3 Ω AC impedance at 50/60 Hz so the CT reference stays rock-steady.
3Solder bidirectional TVS directly across the CT terminal block
SMBJ15CA stays completely invisible during ±1.5 V normal operation yet clamps open-burden faults instantaneously.
4Sample at ≥ 2 kHz and compute true RMS after subtracting DC bias
Subtract the running mean of each full mains cycle before squaring so Vref/2 resistor tolerance introduces zero error.
3. 현장 트러블슈팅 및 멀티미터 점검
| 증상 | 근본 원인 | 멀티미터 점검 | 조치 방법 |
|---|---|---|---|
| RMS reading flattens out above 60 A even though load is 100 A | Burden resistor too large — AC peaks clipping at 0 V and 3.3 V rails | Inspect ADC pin on oscilloscope for flat-topped sine wave | Reduce R_B (e.g. 68 Ω → 33 Ω) and recalibrate firmware scale factor |
4. 자주 묻는 엔지니어링 질문 (FAQ)
Can a CT measure DC battery or solar current?
No — a transformer requires changing magnetic flux (AC). For DC current, use a Kelvin shunt amplifier or Hall-effect current sensor.
Why is the 10 µF capacitor on the Vref/2 divider mandatory?
Without it, the 10 kΩ || 10 kΩ = 5 kΩ divider impedance sits in series with the CT burden, collapsing the AC signal into a tiny fraction.
5. 관련 계산기, 비교 가이드 및 다른 센서 회로
- 변류기(CT) 부담 계산기
- ADC 분해능 계산기
- 포토다이오드 트랜스임피던스 증폭기 (TIA) 회로
- 하이사이드 vs 로우사이드 켈빈 전류 션트 증폭 회로
- 압전 / IEPE (ICP) 정전류 바이어스 & AC 커플링 회로
- 히스테리시스 비교기 (슈미트 트리거) 임계값 검출 회로
- SAR ADC RC 차지 버킷(킥백) 필터 & 세틀링 시간 검증
- 3전극 전기화학 가스 센서(CO / O2 / H2S) 포텐시오스탯
- 압전 차지 앰프 (동축 케이블 정전용량 무관 전하 증폭)
- PNP (소싱) 3선식 센서 출력 회로 시뮬레이터
- NPN (싱킹 / 오픈컬렉터) 3선식 센서 출력 회로
- NAMUR 2선식 본질안전 방폭 센서 회로 (IEC 60947-5-6)
- 2선식 4–20 mA 전류 루프 & ADC 보호 수신 회로